F300 | F301 |
PWM Carrier Frequency
Program ⇒ Special Control Parameters ⇒ Carrier Frequency
This parameter sets the frequency of the pulse width modulation signal applied to the motor.
Note: The carrier frequency must be 2.2 kHz or above except when operating in the Constant Torque, Variable Torque, or the 5- Point Setting modes.
Note: The maximum Carrier Frequency setting allowed is 5.0 kHz for the following ASDs:
The maximum Carrier Frequency setting allowed for all other ASDs is 15 kHz.
Setting the Carrier Frequency above the Derate Threshold frequency (as listed below) for a given ASD will reduce the capability of the ASD.
Direct Access Number — F300
Parameter Type — Numerical
Factory Default — 2.200
Changeable During Run — No
Minimum — 0.500
Maximum —
Units — kHz
|
|
|
| Example |
| ||||
| Derate Threshold Frequency |
|
| |
2.2 kHz | 5.0 kHz | 6.0 kHz | 8.0 kHz | |
| V T 1 3 0 G 7 U |
|
| |
2750B – 215KB | 2500B | 6160B | 2010B | – 2600B |
2750B – 215KB | 2600B | 6400B | 2400B |
|
415KB – 435KB | 4400B | 6400B | 4015B | – 4330B |
415KB – 435KB | 412KB |
| 4500B | – 410KB |
615KB – 635KB | 410KB |
| 4600B | – 4750B |
| 412KB |
| 6015B | – 6120B |
| 610KB |
| 6220B | – 6330B |
| 610KB |
| 6220B | – 6330B |
| 612KB |
| 6500B | – 6750B |
|
|
| 6500B | – 6750B |
Break/Make ST |
|
|
| Direct Access Number — F301 |
Program ⇒ Protection Parameters ⇒ Retry/Restart |
| Parameter Type — Check Box | ||
|
|
|
| Factory Default — Disabled |
This parameter Enables/Disables the ability of the drive to start into a spinning
Changeable During Run — Yes
motor when the ST – CC connection opens momentarily and is then closed (Break/Make ST) or after a power interruption (momentary power failure). This parameter also Enables/Disables F312 and F313.
Settings:
Box checked (Enabled)
Box not checked (Disabled)
G7 ASD Operation Manual | 111 |