F222 | F223 |
RX2 Speed Reference Setpoint #1 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ RX2
This parameter is used to set the direction, gain, and bias of the RX2 input terminal when this terminal is used as the control input while operating in the Speed Control or the Torque Control mode.
Note: The RX2 input terminal may be used with the
Perform the following setup to allow the system to receive control input at the RX2 input terminal:
•Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒ Command Mode ⇒ Use Control Terminal Strip.
•Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒ Frequency Mode #1⇒ Use Option Card RX2.
•Provide a Run command (F or R).
Gain and Bias Settings
When operating in the Speed Control mode, the settings that determine the direction, gain, and bias of the RX2 terminal are:
•RX2 Speed Reference Setpoint #1 (frequency) (F223),
•the RX2 input signal level that represents RX2 Speed Reference Setpoint #1 (frequency): F222,
•RX2 Speed Reference Setpoint #2 (frequency) (F225), and
•the RX2 input signal level that represents RX2 Speed Reference Setpoint #2 (frequency): F224.
When operating in the Torque Control mode, the settings that determine the direction, gain, and bias of the RX2 terminal are:
•RX2 Torque Reference Setpoint #1 (%) (F226),
•the RX2 input signal level that represents the RX2 Torque Reference Setpoint #1 (%): F222,
•RX2 Torque Reference Setpoint #2 (%) (F227), and
•the RX2 input signal level that represents the RX2 Torque Reference Setpoint #2 (%): F224.
Direct Access Number — F222
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
Maximum — 100.0
Units — %
Frequency Settings
Torque Settings
Once set, as the RX2 input voltage changes, the directional information, the output frequency, or the output torque of the drive will vary in accordance with the above settings.
This parameter sets the RX2 input level that represents RX2 Reference Setpoint #1 (frequency) (direction/torque/frequency). This value is entered as
The input signal may be trimmed using F476 (Bias) and F477 (Gain).
RX2 Speed Reference Setpoint #1 (frequency) | Direct Access Number — F223 |
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference | Parameter Type — Numerical |
Setpoints ⇒ RX2 | Factory Default — 0.0 |
This parameter is used to set the direction, gain, and bias of the RX2 input | Changeable During Run — Yes |
| |
terminal when this terminal is used as the control input while operating in the | Minimum — |
Speed Control mode. | Maximum — +80.0 |
| |
See F222 for further information on this setting. | Units — Hz |
This parameter sets RX2 Speed Reference Setpoint #1 (frequency) and is the |
|
frequency that is associated with the setting of F222. |
|
G7 ASD Operation Manual | 99 |