F222

F223

RX2 Speed Reference Setpoint #1 (%)

Program Frequency Setting Parameters Speed Reference Setpoints RX2

This parameter is used to set the direction, gain, and bias of the RX2 input terminal when this terminal is used as the control input while operating in the Speed Control or the Torque Control mode.

Note: The RX2 input terminal may be used with the ASD-Multicomoption board only.

Perform the following setup to allow the system to receive control input at the RX2 input terminal:

Program Fundamental Parameters Standard Mode Selection Command Mode Use Control Terminal Strip.

Program Fundamental Parameters Standard Mode Selection Frequency Mode #1Use Option Card RX2.

Provide a Run command (F or R).

Gain and Bias Settings

When operating in the Speed Control mode, the settings that determine the direction, gain, and bias of the RX2 terminal are:

RX2 Speed Reference Setpoint #1 (frequency) (F223),

the RX2 input signal level that represents RX2 Speed Reference Setpoint #1 (frequency): F222,

RX2 Speed Reference Setpoint #2 (frequency) (F225), and

the RX2 input signal level that represents RX2 Speed Reference Setpoint #2 (frequency): F224.

When operating in the Torque Control mode, the settings that determine the direction, gain, and bias of the RX2 terminal are:

RX2 Torque Reference Setpoint #1 (%) (F226),

the RX2 input signal level that represents the RX2 Torque Reference Setpoint #1 (%): F222,

RX2 Torque Reference Setpoint #2 (%) (F227), and

the RX2 input signal level that represents the RX2 Torque Reference Setpoint #2 (%): F224.

Direct Access Number — F222

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -100.0

Maximum — 100.0

Units — %

Frequency Settings

Torque Settings

Once set, as the RX2 input voltage changes, the directional information, the output frequency, or the output torque of the drive will vary in accordance with the above settings.

This parameter sets the RX2 input level that represents RX2 Reference Setpoint #1 (frequency) (direction/torque/frequency). This value is entered as -100 to +100% of the -10 to +10 VDC RX2 input signal range.

The input signal may be trimmed using F476 (Bias) and F477 (Gain).

RX2 Speed Reference Setpoint #1 (frequency)

Direct Access Number — F223

Program Frequency Setting Parameters Speed Reference

Parameter Type — Numerical

Setpoints RX2

Factory Default — 0.0

This parameter is used to set the direction, gain, and bias of the RX2 input

Changeable During Run — Yes

 

terminal when this terminal is used as the control input while operating in the

Minimum — -80.0

Speed Control mode.

Maximum — +80.0

 

See F222 for further information on this setting.

Units — Hz

This parameter sets RX2 Speed Reference Setpoint #1 (frequency) and is the

 

frequency that is associated with the setting of F222.

 

G7 ASD Operation Manual