Preparing for installation

Service access specifications

Parameter

English value

Metric value

 

 

 

 

 

 

Front

36 inches

91 centimeters

 

 

 

Rear

36 inches

91 centimeters

 

 

 

Left

36 inches

91 centimeters

 

 

 

Right

36 inches

91 centimeters

 

 

 

Environmental specifications

For the most reliable system operation:

The room must have sufficient air conditioning capacity to support the cooling needs of the entire system.

The air conditioning system must have controls that prevent excessive temperature changes.

Do not turn on the computer until it has acclimated to the room temperature for at least 24 hours.

Follow the guidelines in the table below for temperature, humidity, and altitude limits for units in operation and for units that are not in operation (that is, units that are in transit or in storage).

Parameter

Operating

Nonoperating

(in service)

(not in service)

 

 

 

 

 

 

 

Temperature

41°F to 95°F (5°C to 35°C)

-4°F to 140°F (-20°C to 60°C)

 

IEC 68-2-1, 68-2-2

IEC 68-2-1, 68-2-2

 

 

 

Humidity

20% to 80% RH

93% RH

(max)

noncondensing; 27°C max wb

noncondensing at 40°C

 

IEC 68-2-2, 68-2-3

IEC 68-2-2, 68-2-3

 

 

 

Altitude (max)

10,000 feet (3 kilometers)

40,000 feet (12 kilometers)

 

IEC 68-2-40, 68-2-41

IEC 68-2-40, 68-2-41

 

 

 