90 G7 ASD Operation Manual
Custom V/f Five-Point Setting #3 Frequency
Program Special Control Parameters V/f Five-Point Setting
The Custom V/f Five Point Setting #3 Frequency se ts the frequency to be
associated with parameter F195 (Custom V/f Five Point Setting #3 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number — F194
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Custom V/f Five-Point Setting #3 Voltage
Program Special Control Parameters V/f Five-Point Setting
The Custom V/f Five-Point Setting #3 Voltage establishes the percentage of
the output voltage that is to be as so ciated with the frequency se tt ing of F194
(Custom V/f Five Point Setting #3 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number — F195
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #4 Frequency
Program Special Control Parameters V/f Five-Point Setting
The Custom V/f Five Point Setting #4 Frequency se ts the frequency to be
associated with parameter F197 (Custom V/f Five Point Setting #4 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number — F196
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Custom V/f Five-Point Setting #4 Voltage
Program Special Control Parameters V/f Five-Point Setting
The Custom V/f Five-Point Setting #4 Voltage establishes the percentage of
the output voltage that is to be as so ciated with the frequency se tt ing of F196
(Custom V/f Five Point Setting #4 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number — F197
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #5 Frequency
Program Special Control Parameters V/f Five-Point Setting
The Custom V/f Five Point Setting #5 Frequency se ts the frequency to be
associated with parameter F199 (Custom V/f Five Point Setting #5 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number — F198
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Custom V/f Five-Point Setting #5 Voltage
Program Special Control Parameters V/f Five-Point Setting
The Custom V/f Five-Point Setting #5 Voltage establishes the percentage of
the output voltage that is to be as so ciated with the frequency se tt ing of F198
(Custom V/f Five Point Setting #5 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number — F199
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
F194 F199