F704 |
| F721 | |
|
|
| |
Accel/Decel Special Display Resolution | Direct Access Number — | F704 | |
Program ⇒ Special Control Parameters ⇒ Accel/Decel Special | Parameter Type — Numerical | ||
This parameter sets the number of decimal places to be displayed for Accel/ | Factory Default — 0.1 |
| |
Changeable During Run — Yes | |||
Decel functions. | |||
|
| ||
| Minimum — 1 |
| |
| Maximum — 0.01 |
| |
|
|
| |
Prohibit Initializing User Parameters During Typeform | Direct Access Number — | F709 | |
Initialization | Parameter Type — Selection List | ||
Program ⇒ Special Control Parameters ⇒ Special Parameters⇒ | Factory Default — Allowed |
| |
Prohibit Initializing User Parameters During Typeform Initialization | Changeable During Run — Yes | ||
| |||
This parameter Enables/Disables the ability to initialize user parameters during |
|
| |
a Type Form initialization. |
|
| |
Settings: |
|
| |
Allowed |
|
| |
Prohibited |
|
| |
|
|
| |
V/f Group | Direct Access Number — | F720 | |
No path available (Direct Access Only) | Parameter Type — Selection List | ||
| Factory Default — 1 |
|
While operating using the LED Keypad Option 1 of 4 V/f groups may be
Changeable During Run — Yes
selected and run. Each V/f group is comprised of 4
Settings:
Group 1
Group 2
Group 3
Group 4
Note: If using the LCD EOI, press ESC from the Frequency
Command screen to access this parameter.
Stop Pattern
No path available (Direct Access Only)
While operating using the LED Keypad Option the Stop Pattern parameter determines the method used to stop the motor when the stop command is issued via a Stop command from the LED Keypad.
The Decel Stop setting enables the Dynamic Braking system that is setup at F304 or the DC Injection Braking system that is setup at F250, F251, and
F252.
The Coast Stop setting allows the motor to stop at the rate allowed by the inertia of the load.
Settings:
Decel Stop
Coast Stop
Direct Access Number — F721
Parameter Type — Selection List
Factory Default — Decel Stop
Changeable During Run — Yes
Note: The Stop Pattern setting has no effect on the Emergency Off settings of F603. If using the LCD EOI, press ESC from the Frequency Command screen to access this parameter.
G7 ASD Operation Manual | 165 |