F190 | F193 |
Custom V/f Five-Point Setting #1 Frequency
Program ⇒ Special Control Parameters ⇒ V/f
The Custom V/f
The V/f
To enable this function, set the V/f Pattern (F015) selection to Custom V/f Curve.
Custom V/f Curves may be useful in starting high inertia loads such as rotary drum vacuum filters.
Direct Access Number — F190
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Custom V/f Five-Point Setting #1 Voltage
Program ⇒ Special Control Parameters ⇒ V/f
The Custom V/f
See F190 for additional information on custom V/f curves.
Direct Access Number — F191
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #2 Frequency
Program ⇒ Special Control Parameters ⇒ V/f
The Custom V/f Five Point Setting #2 Frequency sets the frequency to be associated with parameter F193 (Custom V/f Five Point Setting #2 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number — F192
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Custom V/f Five-Point Setting #2 Voltage
Program ⇒ Special Control Parameters ⇒ V/f
The Custom V/f
See F190 for additional information on custom V/f curves.
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
G7 ASD Operation Manual | 89 |