F310

F313

Ridethrough Time

Program Protection Parameters Retry/Restart

In the event of a momentary power outage, this parameter determines the length of the Ridethrough time. During a Ridethrough, regenerative energy is used to maintain the control circuitry settings; it is not used to drive the motor.

The Ridethrough will be maintained for the number of seconds set using this parameter.

Note: The actual Ridethrough Time is load-dependent.

Direct Access Number — F310

Parameter Type — Numerical

Factory Default — 2.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 320.0

Units — Seconds

Disable Forward Run/Disable Reverse Run

Direct Access Number —

F311

Program Frequency Setting Parameters Forward/Reverse

Parameter Type — Check Box

Disable

Factory Default — Disabled

 

This parameter Enables/Disables the Forward Run or Reverse Run mode.

Changeable During Run — No

 

 

If either direction is disabled (box checked), commands received for the

 

 

disabled direction will not be recognized.

 

 

If both directions are disabled (both boxes checked), the received direction

 

 

command will determine the direction of the motor rotation.

 

 

Settings:

 

 

Disabled

 

 

Enabled

 

 

 

 

 

Scan Rate

Direct Access Number —

F312

Program Protection Parameters Retry/Restart

Parameter Type — Numerical

In the event of a momentary power outage, the output signal of the drive will

Factory Default — (ASD-dependent)

 

 

cease. Upon restoration of power, the drive will output a low-level signal that

Changeable During Run — No

will be used to determine the rotation speed of the rotor.

Minimum — 0.50

 

The low-level signal will start scanning the motor at FH and decrease until it

 

Maximum — 2.50

 

reaches 0.0 Hz or it matches the signal produced by the turning rotor. Once the

 

 

 

rate of rotation is determined, the drive will provide the normal output to

 

 

engage the motor from its present speed.

 

 

This parameter determines the rate at which the scanning signal goes from FH

 

 

to 0.0 Hz. See F301 for additional information on this parameter.

 

 

 

 

 

Lock-on Rate

Direct Access Number —

F313

Program Protection Parameters Retry/Restart

Parameter Type — Numerical

After a momentary power outage, the ASD may have to startup into a spinning

Factory Default — (ASD-dependent)

 

 

motor. The Lock On Rate is the difference between the time that the RPM of

Changeable During Run — No

the motor is determined by the ASD and the time that the ASD outputs a drive

Minimum — 0.50

 

signal to the motor.

 

 

 

Maximum — 2.50

See F301 for additional information on this parameter.

114

G7 ASD Operation Manual

Page 120
Image 120
Toshiba G7 manual Ridethrough Time, Disable Forward Run/Disable Reverse Run, Scan Rate, Lock-on Rate