F310 | F313 |
Ridethrough Time
Program ⇒ Protection Parameters ⇒ Retry/Restart
In the event of a momentary power outage, this parameter determines the length of the Ridethrough time. During a Ridethrough, regenerative energy is used to maintain the control circuitry settings; it is not used to drive the motor.
The Ridethrough will be maintained for the number of seconds set using this parameter.
Note: The actual Ridethrough Time is
Direct Access Number — F310
Parameter Type — Numerical
Factory Default — 2.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 320.0
Units — Seconds
Disable Forward Run/Disable Reverse Run | Direct Access Number — | F311 |
Program ⇒ Frequency Setting Parameters ⇒ Forward/Reverse | Parameter Type — Check Box | |
Disable | Factory Default — Disabled |
|
This parameter Enables/Disables the Forward Run or Reverse Run mode. | Changeable During Run — No | |
|
| |
If either direction is disabled (box checked), commands received for the |
|
|
disabled direction will not be recognized. |
|
|
If both directions are disabled (both boxes checked), the received direction |
|
|
command will determine the direction of the motor rotation. |
|
|
Settings: |
|
|
Disabled |
|
|
Enabled |
|
|
|
|
|
Scan Rate | Direct Access Number — | F312 |
Program ⇒ Protection Parameters ⇒ Retry/Restart | Parameter Type — Numerical | |
In the event of a momentary power outage, the output signal of the drive will | Factory Default — | |
|
| |
cease. Upon restoration of power, the drive will output a | Changeable During Run — No | |
will be used to determine the rotation speed of the rotor. | Minimum — 0.50 |
|
The |
| |
Maximum — 2.50 |
| |
reaches 0.0 Hz or it matches the signal produced by the turning rotor. Once the |
| |
|
| |
rate of rotation is determined, the drive will provide the normal output to |
|
|
engage the motor from its present speed. |
|
|
This parameter determines the rate at which the scanning signal goes from FH |
|
|
to 0.0 Hz. See F301 for additional information on this parameter. |
|
|
|
|
|
| Direct Access Number — | F313 |
Program ⇒ Protection Parameters ⇒ Retry/Restart | Parameter Type — Numerical | |
After a momentary power outage, the ASD may have to startup into a spinning | Factory Default — | |
|
| |
motor. The Lock On Rate is the difference between the time that the RPM of | Changeable During Run — No | |
the motor is determined by the ASD and the time that the ASD outputs a drive | Minimum — 0.50 |
|
signal to the motor. |
| |
|
|
Maximum — 2.50
See F301 for additional information on this parameter.
114 | G7 ASD Operation Manual |