Adjust Accel/Decel Automatically?

When enabled, the G7 adjusts the acceleration and deceleration rates according to the applied load. The acceleration and deceleration times range from 12.5% to 800% of the programmed values for the active acceleration time [e.g., Acceleration Time #1 (F009) and Deceleration Time #1 (F010)].

The motor and the load must be connected prior to selecting Automatic Accel/Decel.

If Automatic Accel/Decel is not enabled, the Acceleration screen will appear followed by the Deceleration screen as shown below.

Acceleration Time

Deceleration Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts per Hertz Setting

This function establishes the relationship between the output frequency and the output voltage.

Settings:

Constant Torque

Variable Torque

Automatic Torque Boost

Sensorless Vector Control (Speed)

Automatic Torque Boost + Automatic Energy Savings

Sensorless Vector Control (Speed) + Automatic Energy Savings

V/f 5-point Setting (Opens 5-point Setting Screen)

Sensorless Vector Control (Speed/Torque Switching)

PG Feedback Vector Control (Speed/Torque Switching)

PG Feedback Vector Control (Speed/Position Switching)

Motor Current Rating

This parameter allows the user to input the full-load amperage (FLA) of the motor. This value is used by the ASD to determine the Thermal Overload protection setting for the motor and may be found on the nameplate of the motor.

G7 ASD Operation Manual