Fault Screen Display

 

Possible Causes

 

 

 

 

 

 

Overheat

Cooling fan inoperative.

 

• Ventilation openings are obstructed.

 

• Internal thermistor is disconnected.

 

 

 

Over Speed

Result of a motor speed that is greater than the commanded speed when using an

 

 

encoder for speed control.

 

• Improper encoder connection or setup information.

 

Defective encoder.

 

 

 

Overtorque

A torque requirement by the load in excess of the setting of F616 or F617 for a

 

 

time longer than the setting of F618.

 

• The ASD is improperly matched to the application.

 

• The load is obstructed.

 

 

 

Overvoltage During Acceleration

Motor running during restart.

 

 

 

Note:

The event that caused the Trip(s) must be corrected or must decrease to less than the threshold

 

value required to cause the trip to allow for a Reset to be recognized. In the event of multiple

 

active trips, the trip displayed will remain until all faults are corrected and all trips are cleared.

 

 

 

Overvoltage During Deceleration

Deceleration time is too short.

 

 

• DBR value is too high.

 

 

• DBR required (DBR setup required).

 

 

• Stall protection is disabled.

 

 

3-phase input voltage is out of specification.

 

 

Input reactance required.

 

 

 

Overvoltage During Run

Load fluctuations.

 

 

3-Phase input voltage out of specification.

 

 

 

PG Type/Connection Error

ASD is configured to receive a signal from a shaft-mounted encoder and no signal

 

 

 

is being received while running.

 

 

• Disconnection at the Encoder circuit.

 

 

• Motor is stopped and is generating torque via torque limit control.

 

 

• ASD is not configured properly.

 

 

 

 

Phantom Fault

 

In a multiple ASD configuration a faulted ASD signals the remaining ASDs that a

 

 

 

fault has occurred and shuts down the non-faulted ASDs.

 

 

 

Position Deviation Error

Operating in the Position Control mode and the resulting position exceeds the

 

 

 

limits of the F631 setting.

 

 

 

 

RAM Fault

 

Internal RAM malfunction.

 

 

 

 

ROM Fault

 

Internal ROM malfunction.

 

 

 

Sink/Source Setting Error

Improperly positioned Sink/Source jumper on the control board or on an option

 

 

 

device.

 

 

Sink/Source configuration of an option device is incorrect.

 

 

 

Torque Proving Fault

Lift-First Pulse Count (F743) adjustment required.

 

 

 

 