Toshiba G7 RS232/RS485 Wire Count, RS232/RS485 Response Delay Time, RS232/RS485 Master Output

Models: G7

1 221
Download 221 pages 24.99 Kb
Page 178
Image 178

F821

F830

 

 

RS232/RS485 Wire Count

Direct Access Number — F821

Program Communication Setting Parameters Communication

Parameter Type — Selection List

Settings

Factory Default — 4

This parameter sets the communications protocol to the 2 or 4 wire method.

Changeable During Run — Yes

 

Changes made to this parameter require that the power be cycled (Off then On)

 

for the changes to take effect.

 

Settings:

 

2 wire

 

4 wire

 

 

 

RS232/RS485 Response Delay Time

Direct Access Number — F825

Program Communication Setting Parameters Communication

Parameter Type — Numerical

Settings

Factory Default — 0.00

This parameter sets the RS232/RS485 response delay time.

Changeable During Run — Yes

 

 

Minimum — 0.00

Changes made to this parameter require that the power be cycled (Off then On)

Maximum — 2.00

for the changes to take effect.

Units — Seconds

 

 

 

RS232/RS485 Master Output

Direct Access Number — F826

Program Communication Setting Parameters Communication

Parameter Type — Selection List

Settings

Factory Default — No Follower (normal

In a master/follower configuration, this setting determines the output parameter

operation)

Changeable During Run — Yes

of the master ASD that will be used to control the applicable follower ASDs.

 

Note: Select No Follower if F806 is configured as a Master Output controller. Otherwise, an EOI failure will result.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

No Follower (normal operation)

Frequency Reference

Output Command Frequency

Torque Command

Output Torque Command

Communication Error

Program Communication Setting Parameters Communication

Error

In the event of a communication error during a transmission, the command that was transmitted may be cleared or held.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

Command Request Cleared

Command Request Held

Direct Access Number — F830

Parameter Type — Selection List

Factory Default — Command Request

Cleared

Changeable During Run — Yes

172

G7 ASD Operation Manual

Page 178