System Operation
Initial Setup
Upon initial system powerup, the Startup Wizard starts automatically. The Startup Wizard assists the user with the initial configuration of the input power settings and the output parameters of the G7 ASD. The ASD may also be setup by directly accessing each of the individual parameters (see the section titled Direct Access Parameter Information on pg. 59).
The Startup Wizard may also be selected and run from the Program menu after the initial startup if required.
The Startup Wizard querys the user for the following information:
1.Run now? (if selected continue on to step #2)/Run next time at power up? (if selected go to Program Mode)/Manually configure? (if selected go to Finish ⇒ Program Mode).
2.The Voltage and Frequency rating of the motor.
3.The Upper Limit frequency.
4.The Lower Limit frequency.
5.Adjust Accel/Decel times automatically? (if Yes, continue from step #8).
6.The Acceleration time.
7.The Deceleration Time.
8.The Volts/Hertz setting.
9.The motor Current rating.
10.The Command source.
11.The Frequency Reference source.
See the section titled Startup Wizard Requirements on pg. 40 for additional information on the Startup Wizard.
Operation (Local)
Note: See F003 for information on Remote operation.
To turn the motor on, perform the following:
1. Press the MON/PRG key until the Frequency
Command screen is displayed.
Frequency Command Screen
2.Press the LocalRemote key to enter the Local
mode (green Local LED illuminates).
3. Turn the Rotary Encoder clockwise until the Frequency Command value is at the desired setting.
4. Press the Run key and the motor runs at the Frequency Command value.
Note: The speed of the motor may be changed while
the motor is running by using the Rotary Encoder to change the Frequency Command value.
5. Press the StopReset key to stop the motor.
38 | G7 ASD Operation Manual |