F007 | F008 |
Type Reset Reset
Program ⇒ Utility Parameters ⇒ Type Reset
This feature assists the user when performing fault analysis or by allowing a quick system setup change when required. Performing a Type Reset results in one of the following
Settings:
None
Auto Setup for 50 Hz Auto Setup for 60 Hz Restore Factory Defaults Clear Trip
Clear Run Timer
New Base Drive Board *Save User Parameters Restore User Parameters Reload EOI Flash Reset EOI Memory
Direct Access Number — F007
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
Note: *User settings that are stored in the memory of the EOI are not saved via the Save User Parameters selection. The unsaved functions include the EOI Option Setups, (Utility Parameters ⇒) Display Units, and (Monitor Setup ⇒) Scrolling Monitor
Select.
Direction (of motor rotation)
No path available (Direct Access Only)
While operating using the LED Keypad Option this parameter sets the direction of motor rotation. This setting may be changed during operation. This setting will not override parameter F311 (Forward/Reverse Disable).
If either direction is disabled via parameter F311, the disabled direction will not be recognized if commanded by the LED Keypad. If both directions are disabled via parameter F311, the direction command from the LED Keypad will determine the direction of the motor rotation.
Settings:
Forward
Reverse
Direct Access Number — F008
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Yes
Note: If using the LCD EOI, press ESC from the Frequency Command screen to access the Motor Direction parameter.
62 | G7 ASD Operation Manual |