F670 | F674 |
AM Terminal Assignment
Program ⇒ Meter Terminal Adjustment Parameters ⇒ AM
This setting determines the output function of the AM analog output terminal. This output terminal produces an output current that is proportional to the magnitude of the function assigned to this terminal. The available assignments for this output terminal are listed in Table 7 on pg. 61.
Direct Access Number — F670
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes
Note: To read voltage at this terminal a 100 – 500Ω resistor is required and must be connected from AM (+) to AM
Current may be read by connecting an ammeter from AM (+) to AM
The AM analog output has a maximum resolution of 1/1024. The AM Terminal Adjustment (F671) must be used to calibrate the output signal for a proper response.
AM Terminal Adjustment
Program ⇒ Meter Terminal Adjustment Parameters ⇒ AM
This function is used to calibrate the AM analog output terminal.
To calibrate the AM analog output, connect a meter (current or voltage) as described at F670. With the drive running at a known frequency, adjust this parameter (F671) until the running frequency produces the desired DC level output at the AM terminal.
Direct Access Number — F671
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Analog 1 Terminal Setting | Direct Access Number — | F672 | |
Program ⇒ Meter Terminal Adjustment Parameters ⇒ Analog 1 | Parameter Type — Selection List | ||
This parameter sets the Analog 1 multifunction programmable terminal to 1 of | Factory Default — Output Voltage | ||
Changeable During Run — Yes | |||
31 possible functions and is available on the ASD Multicom option board only. | |||
|
| ||
Possible assignments for this output terminal are listed in Table 7 on pg. 61. |
|
| |
|
|
| |
Analog 1 Terminal Adjustment | Direct Access Number — | F673 | |
Program ⇒ Meter Terminal Adjustment Parameters ⇒ Analog 1 | Parameter Type — Numerical | ||
This parameter adjusts the coefficient of the Analog 1 circuit to obtain an | Factory Default — 512 |
| |
Changeable During Run — Yes | |||
output that corresponds with a known input. | |||
|
| ||
This function is used in the calibration of external signal measuring devices | Minimum — 1 |
| |
|
| ||
(DVM, counters, etc.). | Maximum — 1280 |
| |
|
|
| |
Analog 2 Terminal Setting | Direct Access Number — | F674 | |
Program ⇒ Meter Terminal Adjustment Parameters ⇒ Analog 2 | Parameter Type — Selection List | ||
This parameter sets the Analog 2 multifunction programmable terminal to 1 of | Factory Default — | ||
Frequency |
| ||
31 possible functions and is available on the ASD Multicom option board only. | Changeable During Run — Yes | ||
|
Possible assignments for this output terminal are listed in Table 7 on pg. 61.
G7 ASD Operation Manual | 163 |