F670

F674

AM Terminal Assignment

Program Meter Terminal Adjustment Parameters AM

This setting determines the output function of the AM analog output terminal. This output terminal produces an output current that is proportional to the magnitude of the function assigned to this terminal. The available assignments for this output terminal are listed in Table 7 on pg. 61.

Direct Access Number — F670

Parameter Type — Selection List

Factory Default — Output Current

Changeable During Run — Yes

Note: To read voltage at this terminal a 100 – 500resistor is required and must be connected from AM (+) to AM (-). The voltage is read across the 100 – 500resistor.

Current may be read by connecting an ammeter from AM (+) to AM (-).

The AM analog output has a maximum resolution of 1/1024. The AM Terminal Adjustment (F671) must be used to calibrate the output signal for a proper response. SW-1may be switched to allow for the full-range output to be either 0 – 1 mA or 4 – 20 mA when providing an output current, or either 0 – 1 or 1 to 7.5 volts when providing an output voltage at this terminal.

AM Terminal Adjustment

Program Meter Terminal Adjustment Parameters AM

This function is used to calibrate the AM analog output terminal.

To calibrate the AM analog output, connect a meter (current or voltage) as described at F670. With the drive running at a known frequency, adjust this parameter (F671) until the running frequency produces the desired DC level output at the AM terminal.

Direct Access Number — F671

Parameter Type — Numerical

Factory Default — 512

Changeable During Run — Yes

Minimum — 1

Maximum — 1280

Analog 1 Terminal Setting

Direct Access Number —

F672

Program Meter Terminal Adjustment Parameters Analog 1

Parameter Type — Selection List

This parameter sets the Analog 1 multifunction programmable terminal to 1 of

Factory Default — Output Voltage

Changeable During Run — Yes

31 possible functions and is available on the ASD Multicom option board only.

 

 

Possible assignments for this output terminal are listed in Table 7 on pg. 61.

 

 

 

 

 

Analog 1 Terminal Adjustment

Direct Access Number —

F673

Program Meter Terminal Adjustment Parameters Analog 1

Parameter Type — Numerical

This parameter adjusts the coefficient of the Analog 1 circuit to obtain an

Factory Default — 512

 

Changeable During Run — Yes

output that corresponds with a known input.

 

 

This function is used in the calibration of external signal measuring devices

Minimum — 1

 

 

 

(DVM, counters, etc.).

Maximum — 1280

 

 

 

 

Analog 2 Terminal Setting

Direct Access Number —

F674

Program Meter Terminal Adjustment Parameters Analog 2

Parameter Type — Selection List

This parameter sets the Analog 2 multifunction programmable terminal to 1 of

Factory Default — Post-compensation

Frequency

 

31 possible functions and is available on the ASD Multicom option board only.

Changeable During Run — Yes

 

Possible assignments for this output terminal are listed in Table 7 on pg. 61.

G7 ASD Operation Manual

163

Page 169
Image 169
Toshiba G7 manual AM Terminal Assignment, AM Terminal Adjustment, Analog 1 Terminal Setting, Analog 1 Terminal Adjustment