CE Compliance Requirements

In addition to the local and regional safety requirements, this section describes additional criteria that must be met to qualify for European Conformity (CE) certification. All relevant apparatus placed on the European market is required to comply to the European Community directive on electromagnetic compatibility (EMC). The following instructions provide a means of compliance for the 7-series of ASDs. A Technical Construction File (TFC) indicates the rationale used to declare compliance and is on file at Toshiba International Corporation, Houston, Texas U.S.A.

EMC Installation Guidelines

All systems placed on the European market are required to comply with the European Community directive regarding electromagnet compatibility (EMC). Toshiba ensures that all systems deployed in the European market have been screened and are in 100% compliance with the following standards:

Radiated Interference: EN 55011 Group 1 Class A

Mains Interference: EN 55011 Group 1 Class A

Radiated Susceptibility: IEC 801-3 1984

Conducted RFI Susceptibility: prEN55101-4 (prIEC801-6) Doc 90/30270

Electrostatic Discharge: IEC801-2 1991

Electrical Fast Transient: IEC 801-4 1988

Surge: IEC1000-4-5 1995 2 KV line-to-line, 4 KV line-to-earth

Voltage Interruption: IEC 1000-4-11

General EMC Guidelines for Consideration

Input filters of the appropriate rating shall be used.

Proper grounding is a requirement.

Grounds shall be kept to the minimum length to accomplish the connection.

Grounds shall have low RF impedance.

A central ground shall employed in a complex system.

Paint or corrosion can hamper good grounding; remove as required.

Keep control and power cabling separated. Minimize exposed (unscreened) cable.

Use 3600 screened connections where possible.

CE Compliant Installation Guidelines

ASDs should be installed in accordance with the following guidelines.

1.Filtering — An input filter shall be used with the ASD. A Schaffner FN258 series input filter of the appropriate rating shall be mounted next to the ASD.

2.Mechanical — The ASD and the associated equipment shall be mounted on a flat metallic backplane. A minimum space of 5 cm (2 inches) shall be between the ASD and the filter to allow for ventilation. The filter output cable is to be connected from the bottom of the filter to the ASD power input and is to be the minimum length required for a connection. See Table 1 on page 11 for filter selection assistance.

10

G7 ASD Operation Manual

Page 16
Image 16
Toshiba G7 manual CE Compliance Requirements, EMC Installation Guidelines, General EMC Guidelines for Consideration