F155 | F162 |
OUT6 On Delay
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays
⇒OUT6
This parameter delays the closing of the OUT6 output terminals by the programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number — F155
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT7 On Delay
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays
⇒OUT7
This parameter delays the closing of the OUT7 output terminals by the programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number — F156
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT1 Off Delay
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays
⇒OUT1
This parameter delays the opening of the OUT1 (A & C) output terminals by the programmed value.
The delay may be increased to allow the devices that are connected to OUT1 to respond.
Direct Access Number — F160
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 Off Delay | Direct Access Number — | F161 |
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays | Parameter Type — Numerical | |
⇒ OUT2 | Factory Default — 2.0 |
|
This parameter delays the opening of the OUT2 (A & C) output terminals by | Changeable During Run — No | |
|
| |
the programmed value (see waveforms at F160). | Minimum — 2.0 |
|
The delay may be increased to allow the devices that are connected to OUT2 to | Maximum — 200.0 |
|
respond. | Units — mS |
|
|
| |
|
|
|
FL Off Delay | Direct Access Number — | F162 |
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Delays | Parameter Type — Numerical | |
⇒ FL | Factory Default — 2.0 |
|
This parameter delays the opening of the FL output terminals by the | Changeable During Run — No | |
|
| |
programmed value (see waveforms at F160). | Minimum — 2.0 |
|
The delay may be increased to allow the devices that are connected to FL to | Maximum — 200.0 |
|
respond. | Units — mS |
|
|
|
84 | G7 ASD Operation Manual |