F130F133

OUT1 Output Terminal Assignment

Direct Access Number — F130

Program Terminal Selection Parameters Output Terminal

Parameter Type — Selection List

Assignment OUT1

Factory Default — Low

This parameter sets the functionality of the OUT1 (A & C) output terminals to

Changeable During Run — No

 

1 of the 60 possible functions that are listed in Table 9 on pg. 81.

 

The on and off delay times of the OUT1 terminals may be adjusted to provide

 

more response time to the device that is connected to the output terminals.

 

In addition, the output terminals must be specified as Normally Open or

 

Normally Closed.

 

 

 

OUT2 Output Terminal Assignment

Direct Access Number — F131

Program Terminal Selection Parameters Output Terminal

Parameter Type — Selection List

Assignment OUT2

Factory Default — RCH (Acc/Dec

This parameter sets the functionality of the OUT2 (A & C) output terminals to

Complete)

Changeable During Run — No

1 of the 60 possible functions that are listed in Table 9 on pg. 81.

 

The on and off delay times of the OUT2 terminals may be adjusted to provide

 

more response time to the device that is connected to the output terminals.

 

In addition, the output terminals must be specified as Normally Open or

 

Normally Closed.

 

 

 

FL Output Terminal Assignment

Direct Access Number — F132

Program Terminal Selection Parameters Output Terminal

Parameter Type — Selection List

Assignment FL

Factory Default — Fault (All)

This parameter sets the functionality of the FL output terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.

The on and off delay times of the FL terminals may be adjusted to provide more response time to the device that is connected to the output terminals.

In addition, the output terminals must be specified as Normally Open or Normally Closed.

Changeable During Run — No

Output #4 Terminal Assignment

Program Terminal Selection Parameters Output Terminal Assignment 4

This parameter sets the functionality of the OUT4 terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.

The on and off delay times of the OUT4 terminals may be adjusted to provide more response time to the device that is connected to the output terminals.

In addition, the output terminals must be specified as Normally Open or Normally Closed.

Direct Access Number — F133

Parameter Type — Selection List

Factory Default — LL

Changeable During Run — No

G7 ASD Operation Manual

79