F130F133
OUT1 Output Terminal Assignment | Direct Access Number — F130 | |
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal | Parameter Type — Selection List | |
Assignment ⇒ OUT1 | Factory Default — Low | |
This parameter sets the functionality of the OUT1 (A & C) output terminals to | Changeable During Run — No | |
| ||
1 of the 60 possible functions that are listed in Table 9 on pg. 81. |
| |
The on and off delay times of the OUT1 terminals may be adjusted to provide |
| |
more response time to the device that is connected to the output terminals. |
| |
In addition, the output terminals must be specified as Normally Open or |
| |
Normally Closed. |
| |
|
| |
OUT2 Output Terminal Assignment | Direct Access Number — F131 | |
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal | Parameter Type — Selection List | |
Assignment ⇒ OUT2 | Factory Default — RCH (Acc/Dec | |
This parameter sets the functionality of the OUT2 (A & C) output terminals to | Complete) | |
Changeable During Run — No | ||
1 of the 60 possible functions that are listed in Table 9 on pg. 81. | ||
| ||
The on and off delay times of the OUT2 terminals may be adjusted to provide |
| |
more response time to the device that is connected to the output terminals. |
| |
In addition, the output terminals must be specified as Normally Open or |
| |
Normally Closed. |
| |
|
| |
FL Output Terminal Assignment | Direct Access Number — F132 | |
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal | Parameter Type — Selection List | |
Assignment ⇒ FL | Factory Default — Fault (All) |
This parameter sets the functionality of the FL output terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.
The on and off delay times of the FL terminals may be adjusted to provide more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or Normally Closed.
Changeable During Run — No
Output #4 Terminal Assignment
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Assignment ⇒ 4
This parameter sets the functionality of the OUT4 terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.
The on and off delay times of the OUT4 terminals may be adjusted to provide more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or Normally Closed.
Direct Access Number — F133
Parameter Type — Selection List
Factory Default — LL
Changeable During Run — No
G7 ASD Operation Manual | 79 |