F675

 

F703

 

 

 

 

 

Analog 2 Terminal Adjustment

Direct Access Number —

F675

 

Program Meter Terminal Adjustment Parameters Analog 2

Parameter Type — Numerical

 

This parameter adjusts the coefficient of the circuit to obtain an output that

Factory Default — 512

 

 

Changeable During Run — Yes

 

corresponds with a known input.

 

 

 

 

This function is used in the calibration of external signal measuring devices

Minimum — 1

 

 

 

 

 

(DVM, counters, etc.).

Maximum — 1280

 

 

 

 

 

 

FP Terminal Setting

Direct Access Number —

F676

 

Program Terminal Selection Parameters FP

Parameter Type — Selection List

 

This parameter commands the multifunction programmable FP terminal to

Factory Default — Output Frequency

 

Changeable During Run — Yes

 

monitor the value of 1 of 31 possible system functions. As the monitored

 

 

 

 

function changes in magnitude or frequency, the pulse count of the FP output

 

 

 

pulse train changes in direct proportion to changes in the monitored function.

 

 

 

As the monitored value goes up so does the pulse count of the FP output.

 

 

 

Note: The duty cycle of the output pulse train remains at 65 ±5.0 µS.

 

 

 

Possible assignments for this output terminal are listed in Table 7 on pg. 61.

 

 

 

 

 

 

 

FP Terminal Adjustment

Direct Access Number —

F677

 

Program Terminal Selection Parameters FP

Parameter Type — Numerical

 

This parameter sets the full-scale reading of the FP Terminal. The full-scale

Factory Default — 3.840

 

 

Changeable During Run — Yes

 

reading of the monitored variable selected in F676 may be set here.

 

 

 

 

 

Minimum — 1.000

 

 

 

Maximum — 43.200

 

 

 

Units — kHz

 

 

 

 

 

 

Display Units for Voltage and Current

Direct Access Number —

F701

 

Program Utility Parameters Display Units

Parameter Type — Selection List

 

This parameter sets the unit of measurement for current and voltage values

Factory Default — %

 

 

Changeable During Run — Yes

 

displayed on the EOI.

 

 

 

 

Settings:

 

 

%

 

 

 

V/A

 

 

 

 

 

 

 

Hz Per User-defined Unit

Direct Access Number —

F702

 

Program Utility Parameters Display Units

Parameter Type — Numerical

 

This parameter allows the user to input a quantity to be displayed on the EOI

Factory Default — 0.00

 

 

Changeable During Run — Yes

 

that is proportional to the output frequency of the drive.

 

 

 

 

This feature is useful when the output of a process is moved along at a rate that

Minimum — 0.00

 

 

 

 

 

is proportional to the output frequency of the drive.

Maximum — 200.0

 

Units — Hz/UDU

Frequency Display Resolution

Program Utility Parameters Display Units

The parameter sets the number of decimal places to be displayed during non- Accel/Decel functions.

Direct Access Number — F703

Parameter Type — Numerical

Factory Default — 0.1

Changeable During Run — Yes

Minimum — 1

Maximum — 0.01

164

G7 ASD Operation Manual

Page 170
Image 170
Toshiba G7 manual Analog 2 Terminal Adjustment, FP Terminal Setting, FP Terminal Adjustment, Hz Per User-defined Unit