164 G7 ASD Operation Manual
Analog 2 Terminal Ad justment
Program Meter Terminal Adjustment Paramet ers Analog 2
This parameter adjusts the coefficient of the circuit to obtain an output that
corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
Direct Access Number F675
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
FP Terminal Setting
Program Terminal Selection Parameters FP
This parameter commands the multifunction programmable FP terminal to
monitor the value of 1 of 31 possible system func tions. As the monitored
function changes in magnitude or frequency, the pulse count of the FP output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the FP output.
Note: The duty cycle of the output pulse train remains at 65 ±5.0 µS.
Possible assignments for thi s output terminal are listed in Table 7 on pg. 61.
Direct Access Number F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
FP Terminal Adjustment
Program Terminal Selection Parameters FP
This parameter sets the full-scale reading of the FP Terminal. The full-scale
reading of the monitored variable selected in F676 may be set here.
Direct Access Number F677
Parameter Type — Numerical
Factory Default — 3.840
Changeable During Run — Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Display Units for Voltage and Current
Program Utility Parameters Displ ay Units
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
%
V/A
Direct Access Number F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Hz Per User-defined Unit
Program Utility Parameters Displ ay Units
This parameter allows the user to input a quantity to be displayed on the EOI
that is proportional to the output frequency of the drive.
This feature is useful when the output of a pro cess is moved along at a rate that
is proportional to the output frequenc y of the drive.
Direct Access Number F702
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
Frequency Display Resolution
Program Utility Parameters Displ ay Units
The parameter sets the number of decimal places to be displayed during non-
Accel/Decel functions.
Direct Access Number F703
Parameter Type — Numerical
Factory Default — 0.1
Changeable During Run — Yes
Minimum — 1
Maximum — 0.01
F675 F703