F733 |
| F800 |
|
|
|
LOD Start Time | Direct Access Number — | F733 |
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function | Parameter Type — Numerical | |
⇒ LOD Start Time | Factory Default — 0.0 |
|
The Low Output Disable Start Time sets the amount of time that the LOD | Changeable During Run — Yes | |
|
| |
Start Level criteria must be met and maintained for the LOD function to be | Minimum — 0.0 |
|
initiated. | Maximum — 3600.0 |
|
|
| |
| Units — Seconds |
|
|
|
|
LOD Setpoint Boost (Hz) | Direct Access Number — | F734 |
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function | Parameter Type — Numerical | |
⇒ LOD Setpoint Boost (Hz) | Factory Default — 0.0 |
|
The Low Output Disable feature adds the | Changeable During Run — Yes | |
|
| |
commanded frequency. | Minimum — 0.0 |
|
Maximum — Max. Freq.
Units — Hz
LOD Boost Time
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒LOD Boost Time
The Low Output Disable Boost Time sets the
Once expired, the LOD Boost function ceases.
Direct Access Number — F735
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
LOD Feedback Level (Hz) | Direct Access Number — F736 |
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function | Parameter Type — Numerical |
⇒ LOD Feedback Level (Hz) | Factory Default — 0.0 |
The Low Output Disable Feedback Level sets a frequency level that, until the | Changeable During Run — Yes |
| |
output of the ASD drops below this setting, the Restart Delay Timer does not | Minimum — 0.0 |
start. | Maximum — Max. Freq. |
| |
| Units — Hz |
LOD Restart Delay Time
Program ⇒ Special Control Parameters ⇒ Low Output Disable Function
⇒LOD Restart Delay Time
The Low Output Disable Restart Delay Time sets the time that, once expired
and all standard ASD requirements are met, normal ASD operation resumes.
Direct Access Number — F737
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 3600.0
Units — Seconds
Communication Baud Rate (logic)
Program ⇒ Communication Setting Parameters ⇒ Communication
Settings
This parameter plays a role in the setup of the communications network by establishing the Baud Rate of the communications link.
The communications network includes other ASDs and Host/Control computers that monitor the status of the ASD(s), transfers commands, and loads or modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.
Direct Access Number — F800
Parameter Type — Numerical
Factory Default — 9600
Changeable During Run — Yes
Minimum — 1200
Maximum — 9600
Units — BPS
G7 ASD Operation Manual | 167 |