F733

 

F800

 

 

 

LOD Start Time

Direct Access Number —

F733

Program Special Control Parameters Low Output Disable Function

Parameter Type — Numerical

LOD Start Time

Factory Default — 0.0

 

The Low Output Disable Start Time sets the amount of time that the LOD

Changeable During Run — Yes

 

 

Start Level criteria must be met and maintained for the LOD function to be

Minimum — 0.0

 

initiated.

Maximum — 3600.0

 

 

 

 

Units — Seconds

 

 

 

 

LOD Setpoint Boost (Hz)

Direct Access Number —

F734

Program Special Control Parameters Low Output Disable Function

Parameter Type — Numerical

LOD Setpoint Boost (Hz)

Factory Default — 0.0

 

The Low Output Disable feature adds the user-input frequency value to the

Changeable During Run — Yes

 

 

commanded frequency.

Minimum — 0.0

 

Maximum — Max. Freq.

Units — Hz

LOD Boost Time

Program Special Control Parameters Low Output Disable Function

LOD Boost Time

The Low Output Disable Boost Time sets the on-time timer for the LOD Boost function.

Once expired, the LOD Boost function ceases.

Direct Access Number — F735

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 3600.0

Units — Seconds

LOD Feedback Level (Hz)

Direct Access Number — F736

Program Special Control Parameters Low Output Disable Function

Parameter Type — Numerical

LOD Feedback Level (Hz)

Factory Default — 0.0

The Low Output Disable Feedback Level sets a frequency level that, until the

Changeable During Run — Yes

 

output of the ASD drops below this setting, the Restart Delay Timer does not

Minimum — 0.0

start.

Maximum — Max. Freq.

 

 

Units — Hz

LOD Restart Delay Time

Program Special Control Parameters Low Output Disable Function

LOD Restart Delay Time

The Low Output Disable Restart Delay Time sets the time that, once expired

and all standard ASD requirements are met, normal ASD operation resumes.

Direct Access Number — F737

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 3600.0

Units — Seconds

Communication Baud Rate (logic)

Program Communication Setting Parameters Communication

Settings

This parameter plays a role in the setup of the communications network by establishing the Baud Rate of the communications link.

The communications network includes other ASDs and Host/Control computers that monitor the status of the ASD(s), transfers commands, and loads or modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Direct Access Number — F800

Parameter Type — Numerical

Factory Default — 9600

Changeable During Run — Yes

Minimum — 1200

Maximum — 9600

Units — BPS

G7 ASD Operation Manual

167

Page 173
Image 173