Fault Screen Display |
| Possible Causes | |
|
|
|
|
|
|
|
|
Motor Overload |
| • | V/f setting needs to be adjusted. |
|
| • | Motor is locked. |
|
| • Continuous operation at low speed. | |
|
| • Load requirement exceeds ability of the motor. | |
|
| • Startup frequency setting adjustment required. | |
|
|
|
|
No Fault |
| • | No active faults. |
|
|
|
|
Option Fault |
| • | Optional device malfunction. |
|
| • Improper system settings (at ASD or optional device). | |
|
| • Loose or improper connection. | |
|
|
| |
Output Current Protection Fault | • | Output current is not within specified limits. | |
|
| • Loose or improper | |
|
|
|
|
Output Phase Loss |
| • | |
|
|
| |
Note: | The event that caused the Trip(s) must be corrected or must decrease to less than the threshold | ||
| value required to cause the trip to allow for a Reset to be recognized. In the event of multiple | ||
| active trips, the trip displayed will remain until all faults are corrected and all trips are cleared. | ||
|
|
| |
Overcurrent During Acceleration | • | V/f setting needs to be adjusted. | |
|
| • Restart from a momentary power outage. | |
|
| • The ASD is starting into a rotating motor. | |
|
| • ASD/Motor not properly matched. | |
|
| • | |
|
| • Accel time too short. | |
|
| • Voltage Boost setting is too high. | |
|
| • | Motor/machine jammed. |
|
| • Mechanical brake engaged while the ASD is running. | |
|
| • ASD current exceeds 340% of the rated FLA on ASDs that are 100 HP or less | |
|
|
| during acceleration. On ASDs that are greater than 100 HP, this fault occurs when |
|
|
| the ASD current exceeds 320% of the rated FLA during acceleration. |
|
|
| |
Overcurrent During Deceleration | • | ||
|
| • Deceleration time is too short. | |
|
| • | Motor/machine jammed. |
|
| • Mechanical brake engaged while the ASD is running. | |
|
| • ASD current exceeds 340% of the rated FLA on ASDs that are 100 HP or less | |
|
|
| during deceleration. On ASDs that are greater than 100 HP, it occurs when the |
|
|
| ASD current exceeds 320% of the rated FLA during deceleration. |
|
|
| |
Overcurrent During Run | • | Load fluctuations. | |
|
| • ASD is operating at an elevated temperature. | |
|
| • ASD current exceeds 340% of the rated FLA on ASDs that are 100 HP or less | |
|
|
| during a |
|
|
| ASDs that are greater than 100 HP, it occurs when the ASD current exceeds 320% |
|
|
| of the rated FLA on a |
|
|
|
|
178 | G7 ASD Operation Manual |