F235 | F241 |
PG Speed Reference Setpoint #1 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ PG
This parameter is used to set the direction, gain, and bias of the PG input terminal when it is used as the
See F234 for further information on this setting.
This parameter sets PG Speed Reference Setpoint #1 (frequency) and is the frequency that is associated with the setting of F234.
Direct Access Number — F235
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
Maximum — +80.0
Units — Hz
PG Speed Reference Setpoint #2 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ PG
This parameter is used to set the direction, gain, and bias of the PG input terminal when it is used as the
See F234 for further information on this setting.
This parameter sets the PG input pulse count that represents Reference Setpoint #1 (direction/speed). The range of values for this parameter is
Direct Access Number — F236
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum —
Maximum — +100.0
Units — %
PG Speed Reference Setpoint #2 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ PG
This parameter is used to set the direction, gain, and bias of the PG input terminal when it is used as the
See F234 for further information on this setting.
This parameter sets PG Speed Reference Setpoint #2 (frequency) and is the frequency that is associated with the setting of F236.
Direct Access Number — F237
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum —
Maximum — +80.0
Units — Hz
Startup Frequency | Direct Access Number — | F240 | |
Program ⇒ Special Control Parameters ⇒ Frequency Control | Parameter Type — Numerical | ||
The output of the drive will remain at 0.0 Hz until the programmed speed value | Factory Default — 0.10 |
| |
Changeable During Run — Yes | |||
exceeds this setting during startup. Once exceeded during startup, the output | |||
|
| ||
frequency of the drive will accelerate to the programmed setting. | Minimum — 0.0 |
| |
Output frequencies below the Startup Frequency will not be output from the | Maximum — 10.0 |
| |
drive during startup. However, once reaching the Startup Frequency, speed | Units — Hz |
| |
values below the Startup Frequency may be output from the drive. |
| ||
|
| ||
|
|
| |
Run Frequency | Direct Access Number — | F241 | |
Program ⇒ Special Control Parameters ⇒ Frequency Control | Parameter Type — Numerical | ||
This parameter establishes a center frequency (Run Frequency) of a frequency | Factory Default — 0.0 |
| |
Changeable During Run — Yes | |||
band. | |||
|
| ||
Parameter F242 provides a | Minimum — 0.0 |
| |
Maximum — Max. Freq. (F011) | |||
establishing a frequency band. | |||
During acceleration, the drive will not output a signal to the motor until the | Units — Hz |
| |
lower level of the band is reached. |
|
|
During deceleration, the drive will continue to output the programmed deceleration output signal to the motor until the lower level of the band is reached; at which time the output will go to 0.0 Hz.
104 | G7 ASD Operation Manual |