104 G7 ASD Operation Manual
PG Speed Reference Setpoint #1 (frequency)
Program Frequency Setting Parameters Speed Reference
Setpoints PG
This parameter is used to set the direction, gai n, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
See F234 for further information on this setti ng .
This parameter sets PG Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with the setting of F234.
Direct Access Number — F235
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
PG Speed Reference Setpoint #2 (%)
Program Frequency Setting Parameters Speed Reference
Setpoints PG
This parameter is used to set the direction, gai n, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
See F234 for further information on this setti ng .
This parameter sets th e PG input pulse count that represent s R eference
Setpoint #1 (direction/speed). The range of values for this parameter is -100 to
+100% of the PG input pulse count range.
Direct Access Number — F236
Parameter Type — Numeri cal
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
PG Speed Reference Setpoint #2 (frequency)
Program Frequency Setting Parameters Speed Reference
Setpoints PG
This parameter is used to set the direction, gai n, and bias of the PG input
terminal when it is used as the Speed/Direction-Control input.
See F234 for further information on this setti ng .
This parameter sets PG Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F236.
Direct Access Number — F237
Parameter Type — Numeri cal
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
Startup Frequency
Program Special Control Parameters Frequency Control
The output of the drive will rema in at 0. 0 H z unt il the programmed speed valu e
exceeds this setting during startup. Onc e exceeded during startup, the output
frequency of the drive will accelerate to the programmed setting.
Output frequencies below the Startup Frequency will not be output from the
drive during startup. However, once reaching the Startup Frequency, speed
values below the Startup Frequency may be output from the drive.
Direct Access Number — F240
Parameter Type — Numeri cal
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.0
Maximum — 10.0
Units — Hz
Run Frequency
Program Special Control Parameters Frequency Control
This parameter establishes a center fre quency (Run Frequency) of a frequency
band.
Parameter F242 provides a plus-or-minus value for the Run Frequency; thus,
establishing a frequency band.
During acceleration, the drive will not output a signal to the motor until the
lower level of the band is reached.
During deceleration, the drive will continue to output the programmed
deceleration output signal to the motor until the lower level of the band is
reached; at which time the output will go to 0.0 Hz.
Direct Access Number — F241
Parameter Type — Numeri cal
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
F235 F241