F103

F105

ST Signal Selection

Program Terminal Selection Parameters Input Special Functions

This parameter is used to set the operation of the Standby (ST) control terminal or any terminal configured as the ST terminal.

Settings:

ST-to-CC Required

ST-to-CC Not Required

Interlock with F/R Terminal

The setting ST-to-CC Required enables the ASD for operation so long as the control terminal ST is connected to CC via a jumper, contact, or other means.

The ST-to-CC Not Required setting allows the ASD to operate without the ST-to-CCconnection. The control terminal ST may be configured for other functions.

The Interlock with F/R Terminal setting configures the F (Forward) and R (Reverse) control terminals for the secondary function of Standby. Closing a set of contacts to either F or R will cause the ASD to accelerate the motor to the programmed setpoint of F or R. Opening the F and R contact will disable the ASD and the motor will coast to a stop. The control terminal ST may be configured for other functions.

Direct Access Number — F103 Parameter Type — Selection List Factory Default — ST – CC Required Changeable During Run — No

R/F Priority Selection

Program Terminal Selection Parameters Input Special Functions

The R/F Priority Selection determines the operation of the ASD if both the R and F control terminals are activated.

Settings:

Reverse

Suspend

The waveforms below depict the motor response for all combinations of the F and R terminal settings if the Reverse option is chosen.

The Suspend setting will decelerate the motor to a stop regardless of the rotation direction when both the F and R control terminals are activated.

Direct Access Number — F105

Parameter Type — Selection List

Factory Default — Reverse

Changeable During Run — No

G7 ASD Operation Manual

69

Page 75
Image 75
Toshiba G7 manual ST Signal Selection, Priority Selection, Direct Access Number F105