F375

 

F379

 

 

 

Current Control Integral Gain

Direct Access Number —

F375

Program Feedback Parameters PG Settings

Parameter Type — Numerical

This parameter sets the degree and rate at which the output frequency will be

Factory Default — (ASD-dependent)

Changeable During Run — No

allowed to change when prompted by changes in the output current.

 

 

The larger the value entered here, the quicker/more the drive responds to

Minimum — 100.0

 

 

 

changes in feedback.

Maximum — 1250

 

 

 

 

Speed Loop Proportional Gain

Direct Access Number —

F376

Program Feedback Parameters PG Settings

Parameter Type — Numerical

This parameter sets the Proportional Gain (sensitivity) of the drive when

Factory Default — (ASD-dependent)

Changeable During Run — Yes

monitoring the PG signal to control speed. The larger the value entered here,

 

 

the more sensitive the drive is to changes in the received feedback and the

Minimum — 3.2

 

quicker it responds.

Maximum — 1000

 

 

 

 

 

 

Speed Loop Integral Gain

Direct Access Number —

F377

Program Feedback Parameters PG Settings

Parameter Type — Numerical

This parameter sets the response time of the Speed Loop Integral Gain. The

Factory Default — (ASD-dependent)

Changeable During Run — Yes

smaller the value here, the more pronounced (quicker) the effect of the integral

 

 

function.

Minimum — 10.0

 

 

Maximum — 200.0

 

 

 

 

Motor Counter Data

Direct Access Number —

F378

Program Feedback Parameters PG Settings

Parameter Type — Selection List

This parameter sets the pulses-per-revolution displayed at the Monitor screen

Factory Default — Selection 0

Changeable During Run — No

when using a shaft-mounted encoder for speed control. This setting is used for

 

 

display purposes only and does not affect the speed control of the system.

Minimum — Selection 0

 

If zero is selected here then the setting at F370 (Electronic Gear Setting)

Maximum — Selection 5

 

determines the pulses-per-revolution to be displayed at the Monitor screen.

 

 

Settings:

 

 

Selection 0 F370 setting

 

 

Selection 1 — 256 pulses/revolution

 

 

Selection 2 — 512 pulses/revolution

 

 

Selection 3 — 1024 pulses/revolution

 

 

Selection 4 — 2048 pulses/revolution

 

 

Selection 5 — 4096 pulses/revolution

 

 

 

 

 

Speed Loop Parameter Ratio

Direct Access Number —

F379

Program Feedback Parameters PG Settings

Parameter Type — Numerical

 

Factory Default — 1.00

 

Contact Toshiba’s Marketing Department for information on this parameter.

Changeable During Run — No Minimum — 0.01 Maximum — 10.00