174 G7 ASD Operation Manual
Alarms

Table 1 0 lists the alarm codes that may be displayed during operation of the G7 ASD. Each alarm code

listed is accompanied by a description and a possible cause. In the event th at the s ource of th e malfunct ion

cannot be determined, contact your Toshiba Sales Representative for further information on the condition

and for an appropriate course of action.

The Alarms are listed in the top-down order that they are checked for activation. Only th e first to be

detected will be displayed on the Frequency Command screen.

Tabl e 10 . G7 Alarms.

EOI

Display Function Description Possible Causes

CM1 Comm1 Error Internal communications error. Improperly programmed ASD.
Improper communications settings.
Improperly connected cables.
CM2 Comm2 Error External communications error.
EMG Emergency Off Output signal from the ASD is
terminated and a brake may be
applied if so configured.
Stop|Reset pressed twice at the EOI.
EOFF command received remotely.
ASD reset required.
MOFF Main
Undervoltage Undervoltage condition at the
3-phase AC input to the ASD. Low 3-phase utility voltage.
OC Over Current ASD output current greater than
F601 setting. Defective IGBT (U, V, or W).
ASD output to the motor is connected incorrectly.
Disconnect the motor and retry.
ASD output phase-to-phase short.
The ASD is starting into a spinning motor.
Motor/machine jammed.
Mechanical brake engaged while the ASD is starting or
while running.
Accel/Decel time is too short.
Voltage Boost setting is too high.
Load fluctuations.
ASD operating at an elevated temperature.
*OH Overheat ASD ambient temperature
excessive. ASD is operating at an elevated temperature.
ASD is too close to heat-generating equipment.
Cooling fan vent is obstructed (see Mounting the ASD
on pg. 18).
Cooling fan is inoperative.
Internal thermistor is disconnected.
OJ Timer Run-time counter exceeded. Type R ese t required; select Clear run timer.
* Reset ignored if acti ve.