Alarms
Table 10 lists the alarm codes that may be displayed during operation of the G7 ASD. Each alarm code listed is accompanied by a description and a possible cause. In the event that the source of the malfunction cannot be determined, contact your Toshiba Sales Representative for further information on the condition and for an appropriate course of action.
The Alarms are listed in the
Table 10. G7 Alarms.
EOI | Function | Description |
| Possible Causes | |
Display |
| ||||
|
|
|
| ||
|
|
|
|
| |
CM1 | Comm1 Error | Internal communications error. | • | Improperly programmed ASD. | |
|
|
| • | Improper communications settings. | |
CM2 | Comm2 Error | External communications error. | |||
• | Improperly connected cables. | ||||
|
|
| |||
|
|
|
|
| |
EMG | Emergency Off | Output signal from the ASD is | • | StopReset pressed twice at the EOI. | |
|
| terminated and a brake may be | • EOFF command received remotely. | ||
|
| applied if so configured. | |||
|
|
|
| ||
|
|
| • | ASD reset required. | |
|
|
|
|
| |
MOFF | Main | Undervoltage condition at the | • | Low | |
| Undervoltage |
|
| ||
|
|
|
|
| |
OC | Over Current | ASD output current greater than | • | Defective IGBT (U, V, or W). | |
|
| F601 setting. | • ASD output to the motor is connected incorrectly. | ||
|
|
| |||
|
|
|
| Disconnect the motor and retry. | |
|
|
| • ASD output | ||
|
|
| • The ASD is starting into a spinning motor. | ||
|
|
| • | Motor/machine jammed. | |
|
|
| • Mechanical brake engaged while the ASD is starting or | ||
|
|
|
| while running. | |
|
|
| • Accel/Decel time is too short. | ||
|
|
| • Voltage Boost setting is too high. | ||
|
|
| • | Load fluctuations. | |
|
|
| • ASD operating at an elevated temperature. | ||
|
|
|
|
| |
*OH | Overheat | ASD ambient temperature | • | ASD is operating at an elevated temperature. | |
|
| excessive. | • ASD is too close to | ||
|
|
| |||
|
|
| • Cooling fan vent is obstructed (see Mounting the ASD | ||
|
|
|
| on pg. 18). | |
|
|
| • Cooling fan is inoperative. | ||
|
|
| • Internal thermistor is disconnected. | ||
|
|
|
|
| |
OJ | Timer | • | Type Reset required; select Clear run timer. | ||
|
|
|
|
| |
* Reset ignored if active. |
|
|
| ||
|
|
|
|
|
174 | G7 ASD Operation Manual |