F171 | F174 |
Motor #2 Max Output Voltage
Program ⇒ Motor Parameters ⇒ Motor Set #2
The Motor #2 Maximum Output Voltage is the Motor #2 output voltage at the Base Frequency (F170). Regardless of the programmed value, the output voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD and the Supply Voltage Compensation setting (F307).
This parameter is used only when the parameters for motor set #2 are configured and selected. Motor set #2 may be selected by a properly configured input terminal.
Direct Access Number — F171
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Motor #2 Torque Boost
Program ⇒ Motor Parameters ⇒ Motor Set #2
The Motor #2 Torque Boost function is used to increase the low frequency torque for high inertia loads by increasing the output voltage at frequencies below ½ of the #2 Base Frequency setting (F170).
See parameter F016 (Motor #1 Torque Boost) for an explanation of torque boost.
This parameter is used only when the parameters for motor set #2 are configured and selected. Motor set #2 may be selected by a properly configured input terminal.
Direct Access Number — F172
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Electronic Thermal Protection #2 | Direct Access Number — | F173 | |
Program ⇒ Motor Parameters ⇒ Motor Set #2 | Parameter Type — Numerical | ||
The Motor #2 Electronic Thermal Protection parameter specifies the motor | Factory Default — 100.0 |
| |
Changeable During Run — Yes | |||
overload current level for motor set #2. This value is entered as either a | |||
|
| ||
percentage of the full load rating of the ASD or as the FLA of the motor. | Minimum — 10.0 |
| |
The unit of measurement for this parameter may be set to Amps (V/A) or it | Maximum — 100.0 |
| |
may be set as a percentage of the ASD rating. The | Units — % |
| |
motor may be entered directly when Amps is selected as the unit of |
| ||
|
| ||
measurement (see F701 to change the display unit). |
|
| |
Electronic Thermal Protection settings (#1 – #4) will be displayed in Amps if |
|
| |
the EOI display units are set to V/A rather than %. |
|
| |
|
|
| |
Motor #3 Base Frequency | Direct Access Number — | F174 | |
Program ⇒ Motor Parameters ⇒ Motor Set #3 | Parameter Type — Numerical | ||
The Motor #3 Base Frequency setting is the frequency at which the output | Factory Default — 60.0 |
| |
Changeable During Run — Yes | |||
voltage of the ASD reaches its maximum setting. The Maximum Output | |||
|
| ||
Voltage is set at F175. | Minimum — 25.0 |
| |
This parameter is used only when the parameters for motor set #3 are | Maximum — 299.0 |
| |
configured and selected. Motor set #3 may be selected by a properly configured | Units — Hz |
| |
|
|
input terminal.
For proper motor operation, the Base Frequency should be set for the name- plated frequency of the motor.
86 | G7 ASD Operation Manual |