70 G7 ASD Operation Manual
Input Terminal Priorit y
Program Terminal Selection Parameters Input Special Functions
This parameter is use d to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Control Terminal Strip even
though the system is in the Local mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Control Terminal Strip will receive priority over
commands from the EOI.
See F260 for further information on using the Jog function.
See F250F252 for further information on DC Injection Braking.
Settings:
Enabled (Box checked)
Disabled
Direct Access Number — F106
Parameter Type — Check Box
Factory Default — Disabled
Changeable During Run — No
Extended Terminal Function
Program Terminal Selection Parameters Input Special Functions
The Extended Terminal Function is used with the optional ASD-Multicom
card only. This parameter defines the format of the binary or BCD data when
using the option card.
Settings:
None
12-Bit Binary
16-Bit Binary
3-Digit BCD
4-Digit BCD
Reverse 12-Bit Binary
Reverse 16-Bit Binary
Reverse 3-Digit BCD
Reverse 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will r equire the configuration of
terminals S1-S4 on the Control Terminal Strip as binary bits 0 – 3 (F115
F118). The Frequency Mod e #1 Selection (F004) must be set to Use Binary/
BCD Input.
For proper scaling of the binary or BCD input, parameters F228F231 must
be configured [BIN Reference Point #1, BIN Reference #1 (frequency), Bin
Reference Point #2, and BIN Reference #2 (fre quency)].
Direct Access Number — F107
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
F106 F107