OUT5 Terminal Assignment
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Assignment ⇒ 5
This parameter sets the functionality of the OUT5 terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.
The on and off delay times of the OUT5 terminals may be adjusted to provide more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or Normally Closed.
Direct Access Number — F134
Parameter Type — Selection List
Factory Default — UL
Changeable During Run — No
OUT6 Terminal Assignment
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal Assignment ⇒ 6
This parameter sets the functionality of the OUT6 terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.
The on and off delay times of the OUT6 terminals may be adjusted to provide more response time to the device that is connected to the output terminals.
In addition, the output terminals must be specified as Normally Open or Normally Closed.
Direct Access Number — F135
Parameter Type — Selection List
Factory Default — RCH (Specified
Speed)
Changeable During Run — No
OUT7 Terminal Assignment | Direct Access Number — | F136 | |
Program ⇒ Terminal Selection Parameters ⇒ Output Terminal | Parameter Type — Selection List | ||
Assignment ⇒ 7 | Factory Default — Overcurrent | ||
This parameter sets the functionality of the OUT7 terminals to 1 of the 60 | Prealarm |
| |
Changeable During Run — No | |||
possible functions that are listed in Table 9 on pg. 81. | |||
|
| ||
The on and off delay times of the OUT7 terminals may be adjusted to provide |
|
| |
more response time to the device that is connected to the output terminals. |
|
| |
In addition, the output terminals must be specified as Normally Open or |
|
| |
Normally Closed. |
|
| |
|
|
| |
F Input Terminal Delay | Direct Access Number — | F140 | |
Program ⇒ Terminal Selection Parameters ⇒ Input Terminal Delays ⇒ | Parameter Type — Numerical | ||
F | Factory Default — 8.0 |
| |
This parameter delays the response of the ASD to any change in the F terminal | Changeable During Run — No | ||
|
| ||
input by the programmed value. | Minimum — 2.0 |
|
Maximum — 200.0
Units — mS
The delay may be increased to provide additional electrical noise immunity or to prevent the ASD from responding to contact bounce or chatter.