OUT5 Terminal Assignment

Program Terminal Selection Parameters Output Terminal Assignment 5

This parameter sets the functionality of the OUT5 terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.

The on and off delay times of the OUT5 terminals may be adjusted to provide more response time to the device that is connected to the output terminals.

In addition, the output terminals must be specified as Normally Open or Normally Closed.

Direct Access Number — F134

Parameter Type — Selection List

Factory Default — UL

Changeable During Run — No

OUT6 Terminal Assignment

Program Terminal Selection Parameters Output Terminal Assignment 6

This parameter sets the functionality of the OUT6 terminals to 1 of the 60 possible functions that are listed in Table 9 on pg. 81.

The on and off delay times of the OUT6 terminals may be adjusted to provide more response time to the device that is connected to the output terminals.

In addition, the output terminals must be specified as Normally Open or Normally Closed.

Direct Access Number — F135

Parameter Type — Selection List

Factory Default — RCH (Specified

Speed)

Changeable During Run — No

OUT7 Terminal Assignment

Direct Access Number —

F136

Program Terminal Selection Parameters Output Terminal

Parameter Type — Selection List

Assignment 7

Factory Default — Overcurrent

This parameter sets the functionality of the OUT7 terminals to 1 of the 60

Prealarm

 

Changeable During Run — No

possible functions that are listed in Table 9 on pg. 81.

 

 

The on and off delay times of the OUT7 terminals may be adjusted to provide

 

 

more response time to the device that is connected to the output terminals.

 

 

In addition, the output terminals must be specified as Normally Open or

 

 

Normally Closed.

 

 

 

 

 

F Input Terminal Delay

Direct Access Number —

F140

Program Terminal Selection Parameters Input Terminal Delays

Parameter Type — Numerical

F

Factory Default — 8.0

 

This parameter delays the response of the ASD to any change in the F terminal

Changeable During Run — No

 

 

input by the programmed value.

Minimum — 2.0

 

Maximum — 200.0

Units — mS

The delay may be increased to provide additional electrical noise immunity or to prevent the ASD from responding to contact bounce or chatter.