F487 | F491 |
Compensation Coefficient for Iron Loss
Program ⇒ Special Control Parameters ⇒ Special Parameters⇒
Compensation Coefficient for Iron Loss
This parameter compensates for losses in the
Direct Access Number — F487
Parameter Type — Numerical
Factory Default — 105.0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Voltage Compensation Coefficient for Dead Time | Direct Access Number — | F488 |
Program ⇒ Special Control Parameters ⇒ Special Parameters⇒ | Parameter Type — Numerical | |
Voltage Compensation Coefficient for Dead Time | Factory Default — 163.8 |
|
This parameter adjusts the degree of voltage compensation during dead time by | Changeable During Run — Yes | |
|
| |
increasing or decreasing the | Minimum — 1.64 |
|
start of the dead time. | Maximum — 327.6 |
|
|
| |
|
|
|
Dead Time Compensation (Enable) | Direct Access Number — | F489 |
Program ⇒ Special Control Parameters ⇒ Special Parameters⇒ Dead | Parameter Type — Selection List | |
Time Compensation | Factory Default — Enabled |
|
This parameter Enables/Disables the Dead Time Compensation function. The | Changeable During Run — Yes | |
|
| |
Dead Time Compensation feature provides a smoothing of the |
|
|
signal that feeds the Gate Driver board during the off portion of the |
|
|
cycle. |
|
|
Settings: |
|
|
Enabled |
|
|
Disabled |
|
|
|
|
|
| Direct Access Number — | F490 |
Program ⇒ Special Control Parameters ⇒ Special Parameters⇒ Dead- | Parameter Type — Numerical | |
time Compensation Bias | Factory Default — 0.000 |
|
This parameter sets a bias for the | Changeable During Run — Yes | |
|
| |
Minimum — |
| |
signal that feeds the Gate Driver board. | Maximum — 32.767 |
|
|
| |
|
|
|
Switching Frequency of Current/Voltage Control | Direct Access Number — | F491 |
Program ⇒ Special Control Parameters ⇒ Special Parameters ⇒ | Parameter Type — Numerical | |
Switching Frequency between Current and Voltage Control | Factory Default — 40.00 |
|
This parameter sets the threshold frequency at which ASD control is switched | Changeable During Run — Yes | |
|
| |
between | Minimum — 10.00 |
|
Maximum — 60.00
Units — Hz
G7 ASD Operation Manual | 139 |