F440

 

F444

 

 

 

Power Running Torque Limit #1

Direct Access Number —

F440

Program Torque Setting Parameters Torque Limit Settings

Parameter Type — Selection List

This parameter determines the source of the control signal for the positive

Factory Default — Setting

 

Changeable During Run — Yes

torque limit setting. If Setting is selected, the value set at F441 is used as the

 

 

Power Running Torque Limit #1 input.

 

 

Settings:

 

 

VI/II

 

 

RR

 

 

RX

 

 

RX2 (option)

 

 

Setting

 

 

 

 

 

Driving Torque Limit #1

Direct Access Number —

F441

Program Torque Setting Parameters Manual Torque Limit

Parameter Type — Numerical

Settings

Factory Default — 250.0

 

This parameter provides a value for the Power Running Torque Limit #1

Changeable During Run — Yes

 

 

setting if Setting is selected at F440. This value provides the positive torque

Minimum — 0.00

 

upper limit for the #1 motor.

Maximum — 250.0

 

 

 

 

Units — %

 

 

 

 

Regeneration Torque Limit #1

Direct Access Number —

F442

Program Torque Setting Parameters Torque Limit Settings

Parameter Type — Selection List

This parameter determines the source of the Regenerative Torque Limit

Factory Default — Setting

 

Changeable During Run — Yes

control signal. If Setting is selected, the value set at F443 is used for this

 

 

parameter.

 

 

Settings:

 

 

VI/II

 

 

RR

 

 

RX

 

 

RX2 (option)

 

 

Setting

 

 

 

 

 

Regeneration Torque Limit Setting #1

Direct Access Number —

F443

Program Torque Setting Parameters Torque Limit Settings

Parameter Type — Numerical

Manual Settings

Factory Default — 250.0

 

This parameter provides a value to be used as the Regeneration Torque Limit

Changeable During Run — Yes

 

 

#1 if Setting is selected at F442.

Minimum — 0.00

 

Maximum — 250.0

Units — %

Driving Torque Limit #2

Program Torque Setting Parameters Manual Torque Limit

Settings

This parameter is used to set the positive torque upper limit for the #2 motor profile when multiple motors are controlled by a single drive or when a single motor is to be controlled by multiple profiles.

Direct Access Number — F444

Parameter Type — Numerical

Factory Default — 250.0

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.0

Units — %

G7 ASD Operation Manual

133

Page 139