F440 |
| F444 | |
|
|
| |
Power Running Torque Limit #1 | Direct Access Number — | F440 | |
Program ⇒ Torque Setting Parameters ⇒ Torque Limit Settings | Parameter Type — Selection List | ||
This parameter determines the source of the control signal for the positive | Factory Default — Setting |
| |
Changeable During Run — Yes | |||
torque limit setting. If Setting is selected, the value set at F441 is used as the | |||
|
| ||
Power Running Torque Limit #1 input. |
|
| |
Settings: |
|
| |
VI/II |
|
| |
RR |
|
| |
RX |
|
| |
RX2 (option) |
|
| |
Setting |
|
| |
|
|
| |
Driving Torque Limit #1 | Direct Access Number — | F441 | |
Program ⇒ Torque Setting Parameters ⇒ Manual Torque Limit | Parameter Type — Numerical | ||
Settings | Factory Default — 250.0 |
| |
This parameter provides a value for the Power Running Torque Limit #1 | Changeable During Run — Yes | ||
|
| ||
setting if Setting is selected at F440. This value provides the positive torque | Minimum — 0.00 |
| |
upper limit for the #1 motor. | Maximum — 250.0 |
| |
|
| ||
| Units — % |
| |
|
|
| |
Regeneration Torque Limit #1 | Direct Access Number — | F442 | |
Program ⇒ Torque Setting Parameters ⇒ Torque Limit Settings | Parameter Type — Selection List | ||
This parameter determines the source of the Regenerative Torque Limit | Factory Default — Setting |
| |
Changeable During Run — Yes | |||
control signal. If Setting is selected, the value set at F443 is used for this | |||
|
| ||
parameter. |
|
| |
Settings: |
|
| |
VI/II |
|
| |
RR |
|
| |
RX |
|
| |
RX2 (option) |
|
| |
Setting |
|
| |
|
|
| |
Regeneration Torque Limit Setting #1 | Direct Access Number — | F443 | |
Program ⇒ Torque Setting Parameters ⇒ Torque Limit Settings ⇒ | Parameter Type — Numerical | ||
Manual Settings | Factory Default — 250.0 |
| |
This parameter provides a value to be used as the Regeneration Torque Limit | Changeable During Run — Yes | ||
|
| ||
#1 if Setting is selected at F442. | Minimum — 0.00 |
|
Maximum — 250.0
Units — %
Driving Torque Limit #2
Program ⇒ Torque Setting Parameters ⇒ Manual Torque Limit
Settings
This parameter is used to set the positive torque upper limit for the #2 motor profile when multiple motors are controlled by a single drive or when a single motor is to be controlled by multiple profiles.
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
G7 ASD Operation Manual | 133 |