OUT1 On Delay

Program Terminal Selection Parameters Output Terminal Delays

OUT1

Once the condition is met to close the OUT1 (A & C) output terminals, this parameter delays the closing of the terminals by the programmed value.

For example, if the OUT1 function is programmed as Overtorque Alarm, OUT1 will close 2.0 mS (the default value for OUT1 On Delay) after the overtorque condition occurs.

The delay may be increased to prevent relay chatter.

Direct Access Number — F150

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT2 On Delay

Program Terminal Selection Parameters Output Terminal Delays

OUT2

This parameter delays the closing of the OUT2 (A & C) output terminals by the programmed value (see waveforms at F150).

The delay may be increased to prevent relay chatter.

Direct Access Number — F151

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

FL On Delay

Program Terminal Selection Parameters Output Terminal Delays

FL

This parameter delays the closing of the FL output terminals by the programmed value (see waveforms at F150).

The delay may be increased to prevent relay chatter.

Direct Access Number — F152

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT4 On Delay

Program Terminal Selection Parameters Output Terminal Delays

OUT4

This parameter delays the closing of the OUT4 output terminals by the programmed value (see waveforms at F150).

The delay may be increased to prevent relay chatter.

Direct Access Number — F153

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

OUT5 On Delay

Program Terminal Selection Parameters Output Terminal Delays

OUT5

This parameter delays the closing of the OUT5 output terminals by the programmed value (see waveforms at F150).

The delay may be increased to prevent relay chatter.

G7 ASD Operation Manual

Direct Access Number — F154

Parameter Type — Numerical

Factory Default — 2.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS