OUT1 On Delay
Program Terminal Selection Parameters Output Terminal Delays
OUT1
Once the condition is met to close the OUT1 (A & C) output terminals, this
parameter delays the closin g of th e terminals by the programmed va lu e.
For example, if the OUT1 function is program me d as Overtorque Alarm,
OUT1 will close 2.0 mS (the default value for OUT1 On Delay) after the
overtorque condition occurs.
The delay may be increased to prevent relay chatter.
Direct Access Number — F150
Parameter Type — Numeri cal
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT2 On Delay
Program Terminal Selection Parameters Output Terminal Delays
OUT2
This parameter delays the closing of the OUT2 (A & C) output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number — F151
Parameter Type — Numeri cal
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
FL On Delay
Program Terminal Selection Parameters Output Terminal Delays
FL
This parameter delays the closing of the FL output terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number — F152
Parameter Type — Numeri cal
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT4 On Delay
Program Terminal Selection Parameters Output Terminal Delays
OUT4
This parameter delays the closing of the OUT4 outpu t terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number — F153
Parameter Type — Numeri cal
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
OUT5 On Delay
Program Terminal Selection Parameters Output Terminal Delays
OUT5
This parameter delays the closing of the OUT5 outpu t terminals by the
programmed value (see waveforms at F150).
The delay may be increased to prevent relay chatter.
Direct Access Number — F154
Parameter Type — Numeri cal
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
F150 F154