G7 ASD Operation Manual 9
Ensure that the Run functions (F, R, Preset Speed, etc.) of the ASD are off before performing a
Reset. The post-reset settings may allow the ASD to start unexpectedly.
Retry or Reset settings may allow the motor to start unexpectedly. Warnings to this effect should
be clearly posted near the ASD and motor.
In the event of a power failure, the motor may restart after power is restored.
Follow all warnings and precautions and do not exceed equipment ratings.
DO NOT install, operate, perform maintenance, or dispose of this equipment until you have read and
understood all of the product warnings and user directions. Failure to do so may result in equipment
damage, operator injury, or loss of life.
Service Life Information
Part Name Service Life Remarks
Large Capacity Electro lytic
Capacitor 5 Years When not used for long periods,
charge semi-annually .
Cooling Fan 26,000 Hours
CN Connectors 100 Connects/Disconnects
On-board Relays 500,000 Actuations