F812

F820

Communications Speed Setpoint #1 (frequency)

Program Communication Setting Parameters Communication

Reference Adjust

This parameter is used to set the gain and bias of the Communications Reference speed control input.

See F811 for further information on this setting.

This parameter sets Communications Reference Speed Setpoint #1.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Direct Access Number — F812

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (F011)

Units — Hz

Communications Reference Setpoint #2 (%)

Direct Access Number —

F813

Program Communication Setting Parameters Communication

Parameter Type — Numerical

Reference Adjust

Factory Default — 100.0

 

This parameter is used to set the gain and bias of the Communications

Changeable During Run — Yes

 

 

Reference speed control input.

Minimum — 0.00

 

See F811 for further information on this setting.

Maximum — 100.0

 

This parameter sets the Communications Reference input value that represents

Units — %

 

 

 

Communications Reference Speed Setpoint #2 (frequency). This value is

 

 

entered as 0 to 100% of the Communications Reference input value range.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

 

 

 

Communications Speed Setpoint #2 (frequency)

Direct Access Number —

F814

Program Communication Setting Parameters Communication

Parameter Type — Numerical

Reference Adjust

Factory Default — 80.0

 

This parameter is used to set the gain and bias of the Communications

Changeable During Run — Yes

 

 

Reference speed control input.

Minimum — 0.0

 

See F811 for further information on this setting.

Maximum — Max. Freq. (F011)

This parameter sets the Communications Reference Speed Setpoint #2.

Units — Hz

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

 

 

 

RS232/RS485 Baud Rate

Direct Access Number —

F820

Program Communication Setting Parameters Communication

Parameter Type — Selection List

Settings

Factory Default — 9600

 

This parameter sets the RS232/RS485 baud rate.

Changeable During Run — Yes

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

1200

2400

4800

9600

19200

38400

G7 ASD Operation Manual