F631 |
| F643 |
|
|
|
Position Difference Limit | Direct Access Number — | F631 |
Program ⇒ Feedback Parameters ⇒ Feedback Settings ⇒ Position | Parameter Type — Numerical | |
Difference Limit | Factory Default — 16.0 |
|
While operating in the Position Control mode, this parameter sets the | Changeable During Run — No | |
|
| |
maximum allowed difference between the commanded position and resulting | Minimum — 0.1 |
|
position as indicated by encoder pulses. | Maximum — 6553 |
|
|
| |
|
|
|
Release After Run Timer | Direct Access Number — | F632 |
Program ⇒ Protection Parameters ⇒ Brake Fault Timer | Parameter Type — Numerical | |
| Factory Default — 0.00 |
|
This parameter sets the time that the brake will hold after the Run command
criteria has been met.
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Alarm Level
Program ⇒ Protection ⇒ Earth Fault Alarm Level
This parameter sets the threshold level (%) that must be exceeded to meet the Earth Fault Alarm activation criteria.
Direct Access Number — F640
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Earth Fault Alarm Time
Program ⇒ Protection ⇒ Earth Fault Alarm Time
In the event that the Earth Fault Alarm activation criteria is met, a timer begins to count down to zero. Upon reaching zero, the Earth Fault Alarm is activated.
This parameter sets the
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Earth Fault Trip Level
Program ⇒ Protection ⇒ Earth Fault Trip Level
This parameter sets the threshold level (%) that must be exceeded to meet the Earth Fault Trip activation criteria.
Direct Access Number — F642
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100
Units — %
Earth Fault Trip Time
Program ⇒ Protection ⇒ Earth Fault Trip Time
In the event that the Earth Fault Trip activation criteria is met, a timer begins to count down to zero. Upon reaching zero, the Earth Fault Trip is activated.
This parameter sets the
Direct Access Number — F643
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.50
Units — Seconds
160 | G7 ASD Operation Manual |