An inductor may be connected across terminals PA and PO to provide additional filtering. When not used, a jumper is connected across these terminals (see Figure 18 on pg. 30).
Connect the input and output power lines of the ASD as shown in Figure 4.
Note: In the event that the motor rotates in the wrong direction when powered up, reverse any two of the three ASD output power leads connected to the motor.
Figure 4. ASD/Motor connection diagram.
Connect the
If multiple conductors are used in parallel for the input or output power and it is necessary to use separate conduits, each parallel set shall have its own conduit and not share its conduit with other parallel sets (i.e., place U1, V1, and W1 in one conduit and U2, V2, and W2 in another) (refer to NEC Article 300.20 and Article 310.4). National and local electrical codes should be referenced if three or more power conductors are run in the same conduit (refer to 2002 NEC Article 310 adjustment factors).
Note: National and local codes should be referenced when running more than three conductors in the same conduit.
Install a molded case circuit breaker (MCCB) or fuse between the
CAUTION
For 600 volt ASDs, the 15 HP or less ASDs (P/N VT130G7U6015B – 6160B) require a
A
External fuses are required on the ASDs listed below when configured for
VT130G7U2600B(DR)
VT130G7U2750B(DR)
VT130G7U412KB(DR)
VT130G7U415KB(DR)
VT130G7U610KB(DR)
VT130G7U612KB(DR)
VT130G7U615KB(DR)
Use either the Ferraz Shawmut Semiconductor fuse (P/N A70QS200) and fuse block P234C, or the Toshiba
20 | G7 ASD Operation Manual |