F514 | F517 |
Accel #4 Time
Program ⇒ Special Control Parameters ⇒ Accel/Decel #1 – #4
Settings
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to the Maximum Frequency for the #4 Acceleration profile. The accel/decel pattern may be set using F502. The minimum accel/decel time may be set using
F508.
Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.
Direct Access Number — F514
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Decel #4 Time
Program ⇒ Special Control Parameters ⇒ Accel/Decel #1 – #4
Settings
This parameter specifies the time in seconds for the drive to go from the Maximum Frequency to 0.0 Hz for the #4 Deceleration profile. The accel/ decel pattern may be set using F502. The minimum accel/decel time may be set using F508.
Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
deceleration time.
Direct Access Number — F515
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Accel/Decel Pattern #4 | Direct Access Number — | F516 | |
Program ⇒ Special Control Parameters ⇒ Accel/Decel #1 – #4 | Parameter Type — Selection List | ||
Settings | Factory Default — Linear |
| |
This parameter enables a | Changeable During Run — Yes | ||
|
| ||
controls the acceleration and deceleration pattern for the #4 Accel/Decel |
|
| |
parameter. |
|
| |
Settings: |
|
| |
Linear |
|
| |
|
| ||
|
| ||
|
|
| |
Accel/Decel Switching Frequency #3 | Direct Access Number — | F517 | |
Program ⇒ Special Control Parameters ⇒ Accel/Decel Special | Parameter Type — Numerical | ||
This parameter sets the frequency at which the acceleration control is switched | Factory Default — 0.00 |
| |
Changeable During Run — Yes | |||
from the Accel #3 profile to the Accel #4 profile during a | |||
|
| ||
profile configuration. | Minimum — 0.00 |
|
Maximum — Max. Freq. (F011)
Units — Hz
144 | G7 ASD Operation Manual |