F514

F517

Accel #4 Time

Program Special Control Parameters Accel/Decel #1 – #4

Settings

This parameter specifies the time in seconds for the drive to go from 0.0 Hz to the Maximum Frequency for the #4 Acceleration profile. The accel/decel pattern may be set using F502. The minimum accel/decel time may be set using

F508.

Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.

Automatic Accel/Decel and Stall settings may lengthen the

acceleration time.

Direct Access Number — F514

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Decel #4 Time

Program Special Control Parameters Accel/Decel #1 – #4

Settings

This parameter specifies the time in seconds for the drive to go from the Maximum Frequency to 0.0 Hz for the #4 Deceleration profile. The accel/ decel pattern may be set using F502. The minimum accel/decel time may be set using F508.

Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.

Automatic Accel/Decel and Stall settings may lengthen the

deceleration time.

Direct Access Number — F515

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Accel/Decel Pattern #4

Direct Access Number —

F516

Program Special Control Parameters Accel/Decel #1 – #4

Parameter Type — Selection List

Settings

Factory Default — Linear

 

This parameter enables a user-selected preprogrammed output profile that

Changeable During Run — Yes

 

 

controls the acceleration and deceleration pattern for the #4 Accel/Decel

 

 

parameter.

 

 

Settings:

 

 

Linear

 

 

S-Pattern 1

 

 

S-Pattern 2

 

 

 

 

 

Accel/Decel Switching Frequency #3

Direct Access Number —

F517

Program Special Control Parameters Accel/Decel Special

Parameter Type — Numerical

This parameter sets the frequency at which the acceleration control is switched

Factory Default — 0.00

 

Changeable During Run — Yes

from the Accel #3 profile to the Accel #4 profile during a multiple-acceleration

 

 

profile configuration.

Minimum — 0.00

 

Maximum — Max. Freq. (F011)

Units — Hz

144

G7 ASD Operation Manual

Page 150
Image 150
Toshiba G7 manual Accel #4 Time, Decel #4 Time, Accel/Decel Pattern #4, Accel/Decel Switching Frequency #3