F233 |
| F234 | |
|
|
| |
BIN Torque Reference Setpoint #2 (%) | Direct Access Number — | F233 | |
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ BIN | Parameter Type — Numerical | ||
This parameter is used to set the direction, gain, and bias of the BIN binary input | Factory Default — +100.0 |
| |
Changeable During Run — Yes | |||
terminals when these terminals are used as the control input while operating in | |||
|
| ||
the Torque Control mode. | Minimum — |
| |
This is accomplished by establishing an associated V/f output pattern for a given | Maximum — +250.0 |
| |
BIN binary input and motor load. | Units — % |
| |
|
| ||
See F232 for further information on this setting. |
|
| |
This parameter sets BIN Torque Reference Setpoint #2 (%) and is entered as |
|
| |
|
| ||
|
|
| |
PG Speed Reference Setpoint #1 (%) | Direct Access Number — | F234 | |
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference | Parameter Type — Numerical | ||
Setpoints ⇒ PG | Factory Default — 0.0 |
| |
This parameter is used to set the direction, gain, and bias of the PG input | Changeable During Run — Yes | ||
|
| ||
terminal when it is used as the Speed/Direction control input. The PG input | Minimum — |
| |
signal is a pulse count originating from a | Maximum — +100.0 |
| |
|
| ||
Note: The PG input terminal may be used with the | Units — % |
| |
|
| ||
option board only. | Frequency Settings |
|
Perform the following setup to allow the system to receive a binary control input:
•Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒ Command Mode ⇒ (any setting).
•Program ⇒ Fundamental Parameters ⇒ Standard Mode Selection ⇒
Frequency Mode #1⇒ Use Pulse Input Option.
• Provide a Run command (F or R).
The settings that determine the direction, gain, and bias of the PG input are:
•PG Speed Reference Setpoint #1 (frequency) (F235),
•the PG input pulse count that represents PG Speed Reference Setpoint #1 (frequency): F234,
•PG Speed Reference Setpoint #2 (frequency) (F237), and
•the PG input pulse count that represents PG Speed Reference Setpoint #2 (frequency): F236.
Once set, as the PG input pulse count changes, the directional information or the output frequency of the drive will vary in accordance with the above settings.
This parameter sets the PG input pulse count that represents Reference Setpoint #1 (frequency) (direction/speed). The range of values for this parameter is
Note: Further
G7 ASD Operation Manual | 103 |