F233

 

F234

 

 

 

BIN Torque Reference Setpoint #2 (%)

Direct Access Number —

F233

Program Torque Setting Parameters Setpoints BIN

Parameter Type — Numerical

This parameter is used to set the direction, gain, and bias of the BIN binary input

Factory Default — +100.0

 

Changeable During Run — Yes

terminals when these terminals are used as the control input while operating in

 

 

the Torque Control mode.

Minimum — -250.0

 

This is accomplished by establishing an associated V/f output pattern for a given

Maximum — +250.0

 

BIN binary input and motor load.

Units — %

 

 

 

See F232 for further information on this setting.

 

 

This parameter sets BIN Torque Reference Setpoint #2 (%) and is entered as

 

 

-250 to +250% of the rated torque.

 

 

 

 

 

PG Speed Reference Setpoint #1 (%)

Direct Access Number —

F234

Program Frequency Setting Parameters Speed Reference

Parameter Type — Numerical

Setpoints PG

Factory Default — 0.0

 

This parameter is used to set the direction, gain, and bias of the PG input

Changeable During Run — Yes

 

 

terminal when it is used as the Speed/Direction control input. The PG input

Minimum — -100.0

 

signal is a pulse count originating from a shaft-mounted Encoder.

Maximum — +100.0

 

 

 

Note: The PG input terminal may be used with the ASD-Multicom

Units — %

 

 

 

option board only.

Frequency Settings

 

Perform the following setup to allow the system to receive a binary control input:

Program Fundamental Parameters Standard Mode Selection Command Mode ⇒ (any setting).

Program Fundamental Parameters Standard Mode Selection

Frequency Mode #1Use Pulse Input Option.

• Provide a Run command (F or R).

The settings that determine the direction, gain, and bias of the PG input are:

PG Speed Reference Setpoint #1 (frequency) (F235),

the PG input pulse count that represents PG Speed Reference Setpoint #1 (frequency): F234,

PG Speed Reference Setpoint #2 (frequency) (F237), and

the PG input pulse count that represents PG Speed Reference Setpoint #2 (frequency): F236.

Once set, as the PG input pulse count changes, the directional information or the output frequency of the drive will vary in accordance with the above settings.

This parameter sets the PG input pulse count that represents Reference Setpoint #1 (frequency) (direction/speed). The range of values for this parameter is -100 to +100% of the PG input pulse count range.

Note: Further application-specific PG settings may be performed from the following path: Program Feedback Parameters PG Settings.

G7 ASD Operation Manual

103

Page 109
Image 109
Toshiba G7 manual BIN Torque Reference Setpoint #2 %, PG Speed Reference Setpoint #1 %