F229 | F232 |
BIN Speed Reference Setpoint #1 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Speed Control mode.
See F228 for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #1 (frequency) and is the frequency that is associated with the setting of F228.
Direct Access Number — F229
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
Maximum — +80.0
Units — Hz
BIN Speed Reference Setpoint #2 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Speed Control or the Torque Control mode.
See F228 for further information on this setting.
This parameter sets BIN Reference Setpoint #2 (direction/torque/frequency) and is entered as 0 to 100% of the BIN binary input word 11111111 (255D).
Direct Access Number — F230
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
BIN Speed Reference Setpoint #2 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Speed Control mode.
See F228 for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #2 (frequency) and is the frequency that is associated with the setting of F230.
Direct Access Number — F231
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum —
Maximum — +80.0
Units — Hz
BIN Torque Reference Setpoint #1 (%)
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given BIN binary input and motor load.
See F228 for further information on this setting.
This parameter sets BIN Torque Reference Setpoint #1 (%) and is entered as
Direct Access Number — F232
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
Maximum — +250.0
Units — %
102 | G7 ASD Operation Manual |