102 G7 ASD Operation Manual
BIN Speed Reference Setpoint #1 (frequency)
Program Frequency Setting Parameters Speed Reference
Setpoints BIN
This parameter is used to s et the direction, gain, a nd bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
See F228 for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with th e setting of F228.
Direct Access Number F229
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
BIN Speed Reference Setpoint #2 (%)
Program Frequency Setting Parameters Speed Reference
Setpoints BIN
This parameter is used to s et the direction, gain, a nd bias of the BIN binary input
terminals when these terminals are used as the control input while operati ng in
the Speed Control or the Torque Control mode.
See F228 for further information on this setting.
This parameter sets BIN Reference Setpoint #2 (direction/t orque/frequency)
and is entered as 0 to 100% of the BIN binary input word 11111111 (255D).
Direct Access Number F230
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
BIN Speed Reference Setpoint #2 (frequency)
Program Frequency Setting Parameters Speed Reference
Setpoints BIN
This parameter is used to s et the direction, gain, a nd bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
See F228 for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with th e setting of F230.
Direct Access Number F231
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum — +80.0
Units — Hz
BIN Torque Reference Setpoint #1 (%)
Program Torque Setting Parameters Setpoints BIN
This parameter is used to s et the direction, gain, a nd bias of the BIN binary input
terminals when these terminals are used as the control input while operati ng in
the Torque Control mode.
This is accomplished by establish ing an as so ciate d V/f out put patt er n for a gi ve n
BIN binary input and motor load.
See F228 for further information on this setting.
This parameter sets BIN Torque Reference Setpoint #1 (%) and is entered as
-250 to +250% of the rated torque.
Direct Access Number F232
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %
F229 F232