F229

F232

BIN Speed Reference Setpoint #1 (frequency)

Program Frequency Setting Parameters Speed Reference Setpoints BIN

This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Speed Control mode.

See F228 for further information on this setting.

This parameter sets BIN Speed Reference Setpoint #1 (frequency) and is the frequency that is associated with the setting of F228.

Direct Access Number — F229

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -80.0

Maximum — +80.0

Units — Hz

BIN Speed Reference Setpoint #2 (%)

Program Frequency Setting Parameters Speed Reference Setpoints BIN

This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Speed Control or the Torque Control mode.

See F228 for further information on this setting.

This parameter sets BIN Reference Setpoint #2 (direction/torque/frequency) and is entered as 0 to 100% of the BIN binary input word 11111111 (255D).

Direct Access Number — F230

Parameter Type — Numerical

Factory Default — 100.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 100.0

Units — %

BIN Speed Reference Setpoint #2 (frequency)

Program Frequency Setting Parameters Speed Reference Setpoints BIN

This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Speed Control mode.

See F228 for further information on this setting.

This parameter sets BIN Speed Reference Setpoint #2 (frequency) and is the frequency that is associated with the setting of F230.

Direct Access Number — F231

Parameter Type — Numerical

Factory Default — +80.0

Changeable During Run — Yes

Minimum — -80.0

Maximum — +80.0

Units — Hz

BIN Torque Reference Setpoint #1 (%)

Program Torque Setting Parameters Setpoints BIN

This parameter is used to set the direction, gain, and bias of the BIN binary input terminals when these terminals are used as the control input while operating in the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a given BIN binary input and motor load.

See F228 for further information on this setting.

This parameter sets BIN Torque Reference Setpoint #1 (%) and is entered as -250 to +250% of the rated torque.

Direct Access Number — F232

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

102

G7 ASD Operation Manual

Page 108
Image 108
Toshiba G7 manual BIN Speed Reference Setpoint #1 frequency, BIN Speed Reference Setpoint #2 %, Direct Access Number F230