F402 |
| F411 | |
|
|
| |
Motor Constant 1 (primary resistance) | Direct Access Number — | F402 | |
Program ⇒ Motor Parameters ⇒ Vector Motor Model | Parameter Type — Numerical | ||
This parameter is the measurement of the stator resistance and is considered a | Factory Default — | ||
Changeable During Run — No | |||
Motor Constant (unchanging). This value is used in conjunction with other | |||
|
| ||
constants to tune the motor. | Minimum — 0.0 |
| |
To use Vector Control, Automatic Torque Boost, or Automatic Energy- | Maximum — 100,000 MΩ |
| |
saving, the Motor Constant setting (motor tuning) is required. | Units — Ω |
| |
|
|
| |
Motor Constant 2 (secondary resistance) | Direct Access Number — | F403 | |
Program ⇒ Motor Parameters ⇒ Vector Motor Model | Parameter Type — Numerical | ||
This parameter is the measurement of the rotor resistance and is considered a | Factory Default — | ||
Changeable During Run — No | |||
Motor Constant (unchanging). This value is used in conjunction with other | |||
|
| ||
constants to tune the motor. | Minimum — 0.00 |
| |
This setting (motor tuning) is required to use the Vector Control, Automatic | Maximum — Open |
| |
Torque Boost, or Automatic | Units — Ω |
| |
|
|
| |
Motor Constant 3 (exciting inductance) | Direct Access Number — | F404 | |
Program ⇒ Motor Parameters ⇒ Vector Motor Model | Parameter Type — Numerical | ||
This parameter is used to input the excitation inductance for the motor. This | Factory Default — | ||
Changeable During Run — No | |||
value is used in conjunction with other constants to tune the motor. | |||
|
| ||
This setting (motor tuning) is required to use the Vector Control, Automatic | Minimum — 0.00 |
| |
|
| ||
Torque Boost, or Automatic | Maximum — 6500.0 |
|
Units — µH
Motor Constant 4 (load inertia)
Program ⇒ Motor Parameters ⇒ Vector Motor Model
This parameter is used to control the load inertia during speed changes. Acceleration and deceleration overshoot may be reduced by increasing this value.
This setting (motor tuning) is required to use the Vector Control, Automatic Torque Boost, or Automatic
Direct Access Number — F405
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Motor Constant 5 (leakage inductance) | Direct Access Number — F410 | |
Program ⇒ Motor Parameters ⇒ Vector Motor Model | Parameter Type — Numerical | |
This parameter provides slight increases in the output voltage of the drive at the | Factory Default — | |
Changeable During Run — No | ||
high speed range. | ||
| ||
This setting (motor tuning) is required to use the Vector Control, Automatic | Minimum — 0.00 | |
| ||
Torque Boost, or Automatic | Maximum — 650.0 | |
|
| |
Number of Poles of Motor | Direct Access Number — F411 | |
Program ⇒ Motor Parameters ⇒ Motor Settings | Parameter Type — Numerical | |
This parameter identifies the number of motor poles. | Factory Default — 4 | |
Changeable During Run — No | ||
| ||
| Minimum — 2 | |
| Maximum — 16 |
128 | G7 ASD Operation Manual |