F411

 

 

 

Motor Constant 1 (primary resistance)

Direct Access Number —

F402

Program Motor Parameters Vector Motor Model

Parameter Type — Numerical

This parameter is the measurement of the stator resistance and is considered a

Factory Default — (ASD-dependent)

Changeable During Run — No

Motor Constant (unchanging). This value is used in conjunction with other

 

 

constants to tune the motor.

Minimum — 0.0

 

To use Vector Control, Automatic Torque Boost, or Automatic Energy-

Maximum — 100,000 M

 

saving, the Motor Constant setting (motor tuning) is required.

Units —

 

 

 

 

Motor Constant 2 (secondary resistance)

Direct Access Number —

F403

Program Motor Parameters Vector Motor Model

Parameter Type — Numerical

This parameter is the measurement of the rotor resistance and is considered a

Factory Default — (ASD-dependent)

Changeable During Run — No

Motor Constant (unchanging). This value is used in conjunction with other

 

 

constants to tune the motor.

Minimum — 0.00

 

This setting (motor tuning) is required to use the Vector Control, Automatic

Maximum — Open

 

Torque Boost, or Automatic Energy-saving functions.

Units —

 

 

 

 

Motor Constant 3 (exciting inductance)

Direct Access Number —

F404

Program Motor Parameters Vector Motor Model

Parameter Type — Numerical

This parameter is used to input the excitation inductance for the motor. This

Factory Default — (ASD-dependent)

Changeable During Run — No

value is used in conjunction with other constants to tune the motor.

 

 

This setting (motor tuning) is required to use the Vector Control, Automatic

Minimum — 0.00

 

 

 

Torque Boost, or Automatic Energy-saving functions.

Maximum — 6500.0

 

Units — µH

Motor Constant 4 (load inertia)

Program Motor Parameters Vector Motor Model

This parameter is used to control the load inertia during speed changes. Acceleration and deceleration overshoot may be reduced by increasing this value.

This setting (motor tuning) is required to use the Vector Control, Automatic Torque Boost, or Automatic Energy-savingfunctions.

Direct Access Number — F405

Parameter Type — Numerical

Factory Default — 1.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 100.0

Motor Constant 5 (leakage inductance)

Direct Access Number — F410

Program Motor Parameters Vector Motor Model

Parameter Type — Numerical

This parameter provides slight increases in the output voltage of the drive at the

Factory Default — (ASD-dependent)

Changeable During Run — No

high speed range.

 

This setting (motor tuning) is required to use the Vector Control, Automatic

Minimum — 0.00

 

Torque Boost, or Automatic Energy-saving functions.

Maximum — 650.0

 

 

Number of Poles of Motor

Direct Access Number — F411

Program Motor Parameters Motor Settings

Parameter Type — Numerical

This parameter identifies the number of motor poles.

Factory Default — 4

Changeable During Run — No

 

 

Minimum — 2

 

Maximum — 16

128

G7 ASD Operation Manual

Page 134
Image 134