F101

F102

Speed Reach Frequency

Program Terminal Selection Parameters Reach Settings

The Speed Reach Frequency sets a frequency threshold that, when reached or is within the bandwidth specified by parameter F102, will provide a signal at an output terminal that can close an appropriately configured output contact (see Table 9 on pg. 81 for the available output assignments).

Direct Access Number — F101

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq. (F011)

Units — Hz

Speed Reach Frequency Tolerance

Program Terminal Selection Parameters Reach Settings

This parameter sets the bandwidth of the Speed Reach Frequency (F101) setting.

Direct Access Number — F102

Parameter Type — Numerical

Factory Default — 2.5

Changeable During Run — Yes

Minimum — 0.0

Maximum — Max. Freq. (F011)

Units — Hz

68

G7 ASD Operation Manual

Page 74
Image 74
Toshiba G7 manual Speed Reach Frequency Tolerance, Direct Access Number F101, Direct Access Number F102