Link Reactor Information

Selection of a link reactor (DCL) is often application specific. This document will provide guidelines for selecting link reactors for the G7 series of drives.

The 600 Volt series drives above 15 HP allow for the reactor to be mounted internal to the drive. All other G7 drives require that the DCL be mounted externally.

When selecting and mounting an external DCL, the air flow around the reactor, the thermal capability of the reactor, the allowable voltage loss, and the amount of harmonic reduction required will be considerations.

Table 21. DCL Selection Table.

Model Number

DCL Part

DCL Inductance

DCL

VT130G7U

Number

(mH)

(Amps)

 

 

 

 

2080B

36350

0.40

30.0

 

 

 

 

2110B

36351

0.30

38.0

 

 

 

 

2160B

36376

0.20

57.0

 

 

 

 

2220B

36353

0.20

76.0

 

 

 

 

2270B

36355

0.10

114

 

 

 

 

4110B

36358

1.30

20.0

 

 

 

 

4160B

36359

0.90

29.0

 

 

 

 

4220B

36360

0.70

39.0

 

 

 

 

4270B

36361

0.50

50.0

 

 

 

 

4330B

36363

0.40

75.0

 

 

 

 

4400B

36364

0.30

88.0

 

 

 

 

4500B

36365

0.20

114.0

 

 

 

 

4600B

36365

0.20

114.0

 

 

 

 

4750B

36366

0.20

141.0

 

 

 

 

410KB

42769

0.14

205.0

 

 

 

 

6060B

36356

2.50

11.0

 

 

 

 

6120B

36359

0.90

29.0

 

 

 

 

6160B

36359

0.90

29.0

 

 

 

 

6220B

36360

0.70

39.0

 

 

 

 

6270B

36362

0.50

55.0

 

 

 

 

6330B

36361

0.50

50.0

 

 

 

 

6400B

36363

0.40

75.0

 

 

 

 

6500B

36363

0.40

75.0

 

 

 

 

6600B

36364

0.30

88.0

 

 

 

 

6750B

36365

0.20

114.0

 

 

 

 

610KB

36366

0.20

141.0

 

 

 

 

612KB

36367

0.15

175.0

 

 

 

 

615KB

41443

0.19

260.0

 

 

 

 

620KB

41443

0.19

260.0

 

 

 

 

625KB

45259

0.10

360.0

 

 

 

 

G7 ASD Operation Manual

199

Page 205
Image 205
Toshiba manual Link Reactor Information, Model Number DCL Part DCL Inductance, VT130G7U Number Amps, 4160B, 4330B