G7 ASD Operation Manual 199
Link Reactor Information
Selection of a link reactor (DCL) is often application specific. This document will provide guidelines for
selecting link reactors for the G7 series of drives.
The 600 Volt series drives above 15 HP allow for the re ac tor to be mounted internal to the drive. All other
G7 drives require that the DCL be mounted externally.
When selecting and mounting an external DCL, the air flow around the reactor, the thermal capability of
the reactor, the allowable voltage loss, and the amount of harmonic reduction required will be
considerations.
Table 21. DCL Selection Table.
Model Number
VT130G7U DCL Part
Number DCL Inductance
(mH) DCL
(Amps)
2080B 36350 0.40 30.0
2110B 36351 0.30 38.0
2160B 36376 0.20 57.0
2220B 36353 0.20 76.0
2270B 36355 0.10 114
4110B 36358 1.30 20.0
4160B 36359 0.90 29.0
4220B 36360 0.70 39.0
4270B 36361 0.50 50.0
4330B 36363 0.40 75.0
4400B 36364 0.30 88.0
4500B 36365 0.20 114.0
4600B 36365 0.20 114.0
4750B 36366 0.20 141.0
410KB 42769 0.14 205.0
6060B 36356 2.50 11.0
6120B 36359 0.90 29.0
6160B 36359 0.90 29.0
6220B 36360 0.70 39.0
6270B 36362 0.50 55.0
6330B 36361 0.50 50.0
6400B 36363 0.40 75.0
6500B 36363 0.40 75.0
6600B 36364 0.30 88.0
6750B 36365 0.20 114.0
610KB 36366 0.20 141.0
612KB 36367 0.15 175.0
615KB 41443 0.19 260.0
620KB 41443 0.19 260.0
625KB 45259 0.10 360.0