Link Reactor Information
Selection of a link reactor (DCL) is often application specific. This document will provide guidelines for selecting link reactors for the G7 series of drives.
The 600 Volt series drives above 15 HP allow for the reactor to be mounted internal to the drive. All other G7 drives require that the DCL be mounted externally.
When selecting and mounting an external DCL, the air flow around the reactor, the thermal capability of the reactor, the allowable voltage loss, and the amount of harmonic reduction required will be considerations.
Table 21. DCL Selection Table.
Model Number | DCL Part | DCL Inductance | DCL |
VT130G7U | Number | (mH) | (Amps) |
|
|
|
|
2080B | 36350 | 0.40 | 30.0 |
|
|
|
|
2110B | 36351 | 0.30 | 38.0 |
|
|
|
|
2160B | 36376 | 0.20 | 57.0 |
|
|
|
|
2220B | 36353 | 0.20 | 76.0 |
|
|
|
|
2270B | 36355 | 0.10 | 114 |
|
|
|
|
4110B | 36358 | 1.30 | 20.0 |
|
|
|
|
4160B | 36359 | 0.90 | 29.0 |
|
|
|
|
4220B | 36360 | 0.70 | 39.0 |
|
|
|
|
4270B | 36361 | 0.50 | 50.0 |
|
|
|
|
4330B | 36363 | 0.40 | 75.0 |
|
|
|
|
4400B | 36364 | 0.30 | 88.0 |
|
|
|
|
4500B | 36365 | 0.20 | 114.0 |
|
|
|
|
4600B | 36365 | 0.20 | 114.0 |
|
|
|
|
4750B | 36366 | 0.20 | 141.0 |
|
|
|
|
410KB | 42769 | 0.14 | 205.0 |
|
|
|
|
6060B | 36356 | 2.50 | 11.0 |
|
|
|
|
6120B | 36359 | 0.90 | 29.0 |
|
|
|
|
6160B | 36359 | 0.90 | 29.0 |
|
|
|
|
6220B | 36360 | 0.70 | 39.0 |
|
|
|
|
6270B | 36362 | 0.50 | 55.0 |
|
|
|
|
6330B | 36361 | 0.50 | 50.0 |
|
|
|
|
6400B | 36363 | 0.40 | 75.0 |
|
|
|
|
6500B | 36363 | 0.40 | 75.0 |
|
|
|
|
6600B | 36364 | 0.30 | 88.0 |
|
|
|
|
6750B | 36365 | 0.20 | 114.0 |
|
|
|
|
610KB | 36366 | 0.20 | 141.0 |
|
|
|
|
612KB | 36367 | 0.15 | 175.0 |
|
|
|
|
615KB | 41443 | 0.19 | 260.0 |
|
|
|
|
620KB | 41443 | 0.19 | 260.0 |
|
|
|
|
625KB | 45259 | 0.10 | 360.0 |
|
|
|
|
G7 ASD Operation Manual | 199 |