F451 |
| F470 | |
|
|
| |
Torque Limit Mode (Speed Dependent) | Direct Access Number — | F451 | |
Program ⇒ Torque Setting Parameters ⇒ Torque Limit Settings ⇒ | Parameter Type — Selection List | ||
Torque Limit Mode (Speed Dependent) | Factory Default — Standard | ||
This parameter allows for either wide or very limited speed fluctuations while | Changeable During Run — Yes | ||
|
| ||
operating in the Torque Control mode. |
|
| |
The ASD output follows the commanded speed when No Speed Cooperation |
|
| |
is selected and has a very limited speed fluctuation range when Standard is |
|
| |
selected. |
|
| |
Settings: |
|
| |
Standard |
|
| |
No Speed Cooperation |
|
| |
|
|
| |
Continued Stall Until Trip During Power Operation | Direct Access Number — | F452 | |
Program ⇒ Protection Parameters ⇒ Stall ⇒ Continuing Stall Period | Parameter Type — Numerical | ||
This parameter allows the user to extend the Overvoltage Stall (F305) and the | Factory Default — 0.0 |
| |
Changeable During Run — Yes | |||
Overcurrent Stall (F017) time settings. | |||
|
| ||
| Minimum — 0.0 |
| |
| Maximum — 1.00 |
| |
| Units — Seconds |
| |
|
|
| |
Stall Prevention During Regeneration | Direct Access Number — | F453 | |
Program ⇒ Protection Parameters ⇒ Stall ⇒ Stall Prevention During | Parameter Type — Selection List | ||
Regeneration | Factory Default — With Stall | ||
This parameter Enables/Disables the Overvoltage Stall (F305) and the | Prevention. |
| |
Changeable During Run — Yes | |||
Overcurrent Stall (F017) function during regeneration only. Application- | |||
|
| ||
specific conditions may occur that warrant disabling the Stall function during |
|
| |
regeneration. |
|
| |
Settings: |
|
| |
With Stall Prevention |
|
| |
Without Stall Prevention |
|
| |
|
|
| |
Current Differential Gain | Direct Access Number — | F454 | |
Program ⇒ Special Control Parameters ⇒ Special Parameters ⇒ | Parameter Type — Numerical | ||
Current Differential Gain | Factory Default — 1.23 |
| |
This parameter determines the degree that the current differential function | Changeable During Run — Yes | ||
|
| ||
affects the output signal. The larger the value entered here, the more | Minimum — 0.00 |
| |
pronounced the Current Differential Gain. | Maximum — 327.6 |
| |
|
| ||
|
|
| |
VI/II Bias Adjust | Direct Access Number — | F470 | |
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference | Parameter Type — Numerical | ||
Setpoints ⇒ VI/II ⇒ Bias | Factory Default — 100 |
|
This parameter is used to
Changeable During Run — Yes
Minimum — 0.0
Note: See note on pg. 46 for further information on the VI/II terminal.
Maximum — 255
This setting may be used to ensure that the zero level of the input source (pot, pressure transducer, flow meter, etc.) is also the zero level setting of the ASD system.
This is accomplished by setting the input source to zero and either increasing or decreasing this setting to provide an output of zero from the ASD.
G7 ASD Operation Manual | 135 |