F810

 

F811

Frequency Point Selection

Direct Access Number —

F810

Program Communication Setting Parameters Communication

Parameter Type — Selection List

Reference Adjust

Factory Default — Disabled

 

This parameter selects the communications reference for scaling.

Changeable During Run — Yes

 

 

See F811 F814 for further information on this setting.

 

 

Note: Scaling the communications signal is not required for all

 

 

applications.

 

 

Changes made to this parameter require that the power be cycled (Off then On)

 

 

for the changes to take effect.

 

 

Settings:

 

 

Disabled

 

 

Common Serial (TTL)

 

 

RS232/RS485

 

 

Communication Card

 

 

Communications Reference Setpoint #1 (%)

Direct Access Number —

F811

Program Communication Setting Parameters Communication

Parameter Type — Numerical

Reference Adjust

Factory Default — 0.00

 

When enabled at F810, this parameter is used to allow the user to set the gain

Changeable During Run — Yes

 

 

and bias of the speed control input to the drive when the speed control signal is

Minimum — 0.00

 

received via the source selected at F810.

Maximum — 100.0

 

 

 

Gain and Bias Settings

Units — %

 

When operating in the Speed Control mode and using one of the control

 

 

sources from Settings above, the settings that determine the gain and bias

 

 

properties of the input signal are:

 

 

Communications Reference Speed Setpoint #1 (frequency)

(F812),

• the communications input signal value that represents Communications Reference Speed Setpoint #1 (frequency): F811,

Communications Reference Speed Setpoint #2 (frequency)

(F814), and

the communications input signal value that represents Communications Reference Speed Setpoint #2 (frequency): F813.

Once set, as the input signal value changes, the output frequency of the drive will vary in accordance with the above settings.

This parameter sets the Communications Reference input value that represents Communications Reference Speed Setpoint #1 (frequency). This value is entered as 0 to 100% of the Communications Reference input value range.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

170

G7 ASD Operation Manual

Page 176