F500 | F501 |
Accel #2 Time
Program ⇒ Special Control Parameters ⇒ #1 – #4 Settings
This parameter specifies the time in seconds for the drive to go from 0.0 Hz to the Maximum Frequency for the #2 Acceleration profile. The accel/decel pattern may be set using F502. The minimum accel/decel time may be set using F508.
This setting is also used to determine the acceleration rate of the Motorized Pot function.
Direct Access Number — F500
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.
Decel #2 Time
Program ⇒ Special Control Parameters ⇒ Accel/Decel #1 – #4
Settings
This parameter specifies the time in seconds for the drive to go from the Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The accel/ decel pattern may be set using F502. The minimum accel/decel time may be set using F508.
This setting is also used to determine the deceleration rate of the Motorized Pot function.
Direct Access Number — F501
Parameter Type — Numerical
Factory Default —
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000
Units — Seconds
Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the
acceleration time.