Accel #2 Time

Program Special Control Parameters #1 – #4 Settings

This parameter specifies the time in seconds for the drive to go from 0.0 Hz to the Maximum Frequency for the #2 Acceleration profile. The accel/decel pattern may be set using F502. The minimum accel/decel time may be set using F508.

This setting is also used to determine the acceleration rate of the Motorized Pot function.

Direct Access Number — F500

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Note: An acceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.

Automatic Accel/Decel and Stall settings may lengthen the

acceleration time.

Decel #2 Time

Program Special Control Parameters Accel/Decel #1 – #4

Settings

This parameter specifies the time in seconds for the drive to go from the Maximum Frequency to 0.0 Hz for the #2 Deceleration profile. The accel/ decel pattern may be set using F502. The minimum accel/decel time may be set using F508.

This setting is also used to determine the deceleration rate of the Motorized Pot function.

Direct Access Number — F501

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Note: A deceleration time shorter than the load will allow may cause nuisance tripping and mechanical stress to loads.

Automatic Accel/Decel and Stall settings may lengthen the

acceleration time.

140

G7 ASD Operation Manual

Page 146
Image 146
Toshiba G7 manual Accel #2 Time, Decel #2 Time, Direct Access Number F500, Direct Access Number F501