F615

 

F620

 

 

 

Overtorque Trip

Direct Access Number —

F615

Program Protection Parameters Overtorque Parameters

Parameter Type — Check Box

This parameter Enables/Disables the Over Torque Tripping function.

Factory Default — Disabled

 

Changeable During Run — No

When enabled, the ASD trips if an output torque value greater than the setting

 

 

of F616 or F617 exists for a time longer than the setting of F618.

 

 

When disabled, the ASD does not trip due to overtorque conditions.

 

 

Settings:

 

 

Disabled

 

 

Enabled (box checked)

 

 

 

 

 

Overtorque Trip/Alarm Level (Positive Torque)

Direct Access Number —

F616

Program Protection Parameters Overtorque Parameters

Parameter Type — Numerical

This parameter sets the torque threshold level that is used as a setpoint for

Factory Default — 150.0

 

Changeable During Run — No

overtorque tripping. This setting is a percentage of the maximum rated torque

 

 

of the drive.

Minimum — 0.00

 

Maximum — 250.0

Units — %

Overtorque Trip/Alarm Level (Negative Torque)

Program Protection Parameters Overtorque Parameters

This parameter sets the torque threshold level that is used as a setpoint for overtorque tripping during regeneration. This setting is a percentage of the maximum rated torque of the drive.

Direct Access Number — F617

Parameter Type — Numerical

Factory Default — 150.0

Changeable During Run — No

Minimum — 0.00

Maximum — 250.0

Units — %

Overtorque Detection Time

Direct Access Number — F618

Program Protection Parameters Overtorque Parameters

Parameter Type — Numerical

This parameter sets the amount of time that the overtorque condition may

Factory Default — 0.50

Changeable During Run — No

exceed the tripping threshold level set at F616 and F617 before a trip occurs.

Minimum — 0.00

 

 

Maximum — 100.0

 

Units — Seconds

 

 

Cooling Fan Control

Direct Access Number — F620

Program Protection Parameters Cooling Fan Settings

Parameter Type — Selection List

This parameter sets the cooling fan run-time command.

Factory Default — Automatic

Changeable During Run — Yes

 

Settings:

 

Automatic

 

Always On

 

G7 ASD Operation Manual

157

Page 163
Image 163
Toshiba G7 manual Overtorque Trip/Alarm Level Positive Torque, Overtorque Trip/Alarm Level Negative Torque