F615 |
| F620 | |
|
|
| |
Overtorque Trip | Direct Access Number — | F615 | |
Program ⇒ Protection Parameters ⇒ Overtorque Parameters | Parameter Type — Check Box | ||
This parameter Enables/Disables the Over Torque Tripping function. | Factory Default — Disabled |
| |
Changeable During Run — No | |||
When enabled, the ASD trips if an output torque value greater than the setting | |||
|
| ||
of F616 or F617 exists for a time longer than the setting of F618. |
|
| |
When disabled, the ASD does not trip due to overtorque conditions. |
|
| |
Settings: |
|
| |
Disabled |
|
| |
Enabled (box checked) |
|
| |
|
|
| |
Overtorque Trip/Alarm Level (Positive Torque) | Direct Access Number — | F616 | |
Program ⇒ Protection Parameters ⇒ Overtorque Parameters | Parameter Type — Numerical | ||
This parameter sets the torque threshold level that is used as a setpoint for | Factory Default — 150.0 |
| |
Changeable During Run — No | |||
overtorque tripping. This setting is a percentage of the maximum rated torque | |||
|
| ||
of the drive. | Minimum — 0.00 |
|
Maximum — 250.0
Units — %
Overtorque Trip/Alarm Level (Negative Torque)
Program ⇒ Protection Parameters ⇒ Overtorque Parameters
This parameter sets the torque threshold level that is used as a setpoint for overtorque tripping during regeneration. This setting is a percentage of the maximum rated torque of the drive.
Direct Access Number — F617
Parameter Type — Numerical
Factory Default — 150.0
Changeable During Run — No
Minimum — 0.00
Maximum — 250.0
Units — %
Overtorque Detection Time | Direct Access Number — F618 | |
Program ⇒ Protection Parameters ⇒ Overtorque Parameters | Parameter Type — Numerical | |
This parameter sets the amount of time that the overtorque condition may | Factory Default — 0.50 | |
Changeable During Run — No | ||
exceed the tripping threshold level set at F616 and F617 before a trip occurs. | ||
Minimum — 0.00 | ||
| ||
| Maximum — 100.0 | |
| Units — Seconds | |
|
| |
Cooling Fan Control | Direct Access Number — F620 | |
Program ⇒ Protection Parameters ⇒ Cooling Fan Settings | Parameter Type — Selection List | |
This parameter sets the cooling fan | Factory Default — Automatic | |
Changeable During Run — Yes | ||
| ||
Settings: |
| |
Automatic |
| |
Always On |
|
G7 ASD Operation Manual | 157 |