Direct Access Parameter Information

The G7 ASD has the ability to allow the user direct access to the motor control functions. The functions listed below have an associated Parameter Number which accesses its setting. There are two ways in which the motor-control parameters may be accessed for modification: Program applicable menu path or Program Direct Access applicable parameter number. Both methods access the parameter via the Program mode. Once accessed, the parameter may be viewed or changed.

The Program mode allows the user to develop an application-specific motor control profile. Motor control functions may be set to accommodate specific power and timing requirements for a given application. The configurable parameters of the Program mode that have user-accessible Parameter Numbers are listed and described below.

Note: The setup procedures included within this section may require a Reset before performing the procedure. Application-specific settings may then be performed. The pre-Reset conditions may be saved (see F007).

Direct Access Parameters/Numbers

Automatic Accel/Decel #1

Program Fundamental Parameters Accel/Decel #1 Settings

This parameter Enables/Disables the ability of the ASD to adjust the acceleration and deceleration rates in accordance with the applied load automatically.

The adjusted acceleration and deceleration times range from 12.5% to 800% of the programmed values for Acceleration Time #1 (F009) and Deceleration Time #1 (F010).

Settings:

Disabled

Enabled (box checked)

Direct Access Number — F000

Parameter Type — Check Box

Factory Default — Disabled

Changeable During Run — No

Note: The motor and the load must be connected prior to selecting Automatic Accel/Decel.

Command Mode Selection

Program Fundamental Parameters Standard Mode Selection

Command Mode

The Command Mode Selection establishes the source of the command input for the ASD. Command inputs include Run, Stop, Forward, etc. The Override feature may supersede the Command Mode Selection setting (see Command Mode and Frequency Mode Control on pg. 31).

Settings:

Use Control Terminal Strip

Use LED Keypad Option

Use Common Serial (TTL)

Use RS232/RS485

Use Communication Card

Direct Access Number — F003

Parameter Type — Selection List

Factory Default — Use Control

Terminal Strip

Changeable During Run — No

G7 ASD Operation Manual

59