G7 ASD Operation Manual 59
Direct Access Parameter Information
The G7 ASD has the ability to allow the user direct access to the motor control functions. The functions
listed below have an associated Paramete r Number which accesses its setting. T here are two ways in
which the motor-control parameters may be accessed for modification: Program applic abl e menu path
or Program Direct Access applicable parameter number. Both methods access the parameter via
the Program mode. Once accessed, the parameter may be viewed or changed.
The Program mode allows the user to develop an application-specific motor control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers are listed and described below.
Note: The setup procedures included within this section may require a Reset before performing the
procedure. Application-specific settings may then be performed. The pre-Reset con d itions may be
saved (see F007).

Direct Access Parameters/Numbers

Automatic Accel/Decel #1
Program Fundamental Parameters Accel/Dece l #1 Settings
This parameter Enables/Disables the ability of the ASD to adjust the
acceleration and deceleration rates in accordance with the applied load
automatically.
The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed va lues for Acceleration Time #1 (F009) and Deceleration
Time #1 (F010).
Settings:
Disabled
Enabled (box checked)
Note: The motor and the load must be connected prior to selecting
Automatic Accel/Decel.
Direct Access Number — F000
Parameter Type — Check Box
Factory Default — Disabled
Changeable During Run — No
Command Mode Se le ction
Program Fundamental Parameters Standard Mode Selection
Command Mode
The Command Mode Selection establishes the source of the com mand input
for the ASD. Command inputs include Run, Stop, Forward, etc. The
Override feature may supersede the Command Mode Selection setting (see
Command Mode and Frequency Mode Control on pg. 31).
Settings:
Use Control Terminal Strip
Use LED Keypad Option
Use Common Serial ( TTL)
Use RS232/RS485
Use Communication Card
Direct Access Number — F003
Parameter Type — Selection List
Factory Default — Use Control
Terminal Strip
Changeable During Run — No
F000 F003