F224 | F227 |
RX2 Speed Reference Setpoint #2 (%)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ RX2
This parameter is used to set the direction, gain, and bias of the RX2 input terminal when this terminal is used as the control input while operating in the Speed Control or the Torque Control mode.
See F222 for further information on this setting.
This parameter sets the RX2 input level that represents RX2 Reference Setpoint #2 (frequency) (direction/torque/frequency). This value is entered as
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum —
Maximum — +100.0
Units — %
RX2 Speed Reference Setpoint #2 (frequency)
Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ RX2
This parameter is used to set the direction, gain, and bias of the RX2 input terminal when this terminal is used as the control input while operating in the Speed Control mode.
See F222 for further information on this setting.
This parameter sets RX2 Speed Reference Setpoint #2 (frequency) and is the frequency that is associated with the setting of F224.
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum —
Maximum — +80.0
Units — Hz
RX2 Torque Reference Setpoint #1 (%)
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ RX2
This parameter is used to set the direction, gain, and bias of the RX2 input terminal when this terminal is used as the control input while operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given RX2 input level and motor load.
See F222 for further information on this setting.
This parameter sets RX2 Torque Reference Setpoint #1 (%) and is the output torque value that is associated with the setting of F222. This value is entered as
Direct Access Number — F226
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum —
Maximum — +250.0
Units — %
RX2 Torque Reference Setpoint #2 (%)
Program ⇒ Torque Setting Parameters ⇒ Setpoints ⇒ RX2
This parameter is used to set the direction, gain, and bias of the RX2 input terminal when this terminal is used as the control input while operating in the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given RX2 input level and motor load.
See F222 for further information on this setting.
This parameter sets RX2 Torque Reference Setpoint #2 (%) and is the output torque value that is associated with the setting of F224. This value is entered as
Direct Access Number — F227
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum —
Maximum — +250.0
Units — %
100 | G7 ASD Operation Manual |