F321

F326

Speed at Drooping Gain 0%

Program Feedback Parameters Drooping Control

This parameter sets the motor speed when at the 0% output torque gain while operating in the Drooping Control mode. This function determines the lowest speed that Drooping will be in effect for motors that share the same load.

Direct Access Number — F321

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 320.0

Units — Hz

Speed at Drooping Gain 100%

Program Feedback Parameters Drooping Control

This parameter sets the motor speed when at the 100% output torque gain while operating in the Drooping Control mode. This function determines the speed of the individual motors at the 100% Drooping Gain setting for motors that share the same load.

Direct Access Number — F322

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 320.0

Units — Hz

Drooping Insensitive Torque Range

Program Feedback Parameters Drooping Control

This parameter defines a torque range in which the Drooping Control settings will be ignored and the programmed torque settings will be followed.

Direct Access Number — F323

Parameter Type — Numerical

Factory Default — 10.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 100.0

Units — %

Drooping Output Filter

Program Feedback Parameters Drooping Control

This parameter is used to set the rate of output change allowed when operating in the Drooping Control mode.

Jerky operation may be decreased by increasing this setting.

Direct Access Number — F324

Parameter Type — Numerical

Factory Default — 100.0

Changeable During Run — Yes

Minimum — 0.1

Maximum — 200.0

Load Inertia (Acc/Dec Torque)

Direct Access Number —

F325

Program Feedback Parameters Drooping Control Load Inertia

Parameter Type — Numerical

This parameter is used for calculating accel/decel torque when compensating

Factory Default — 1.0

 

Changeable During Run — Yes

for load inertia while operating in the Drooping Control mode.

 

 

 

Minimum — 0.0

 

 

Maximum — 1000.0

 

 

 

 

Load Torque Filter (Acc/Dec Torque)

Direct Access Number —

F326

Program Feedback Parameters Drooping Control Load Inertia

Parameter Type — Numerical

This parameter is used to set the response sensitivity when calculating the accel/

Factory Default — 200.0

 

Changeable During Run — Yes

decel torque. This setting applies to load inertia compensation while operating

 

 

in the Drooping Control mode.

Minimum — 0.0

 

This parameter should be gradually adjusted to provide smoother Drooping

Maximum — 200.0

 

Control operation while operating with heavy loads.

 

 