F654 | F661 |
Torque Boost Adjustment
Program ⇒ Terminal Selection Parameters ⇒ Analog Input Functions
This parameter Enables/Disables the feature that allows for the external adjustment of the Torque Boost setting. Selecting either VI/II or RR enables this feature. The selected input is used as a modifier of the programmed Torque Boost setting.
Settings:
Disabled
VI/II
RR
Direct Access Number — F654
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Frequency Override Additive Input | Direct Access Number — | F660 | |
Program ⇒ Feedback Parameters ⇒ Override Control | Parameter Type — Selection List | ||
This parameter Enables/Disables the feature that allows for the external | Factory Default — Disabled |
| |
Changeable During Run — No | |||
adjustment of the Output Frequency. | |||
|
| ||
Selecting either of the input methods listed enables this feature. The selected |
|
| |
input is used as a modifier of the programmed Output Frequency. |
|
| |
Settings: |
|
| |
Disabled |
|
| |
VI/II |
|
| |
RR |
|
| |
RX |
|
| |
RX2 (option) |
|
| |
LED Keypad (option) |
|
| |
Binary/BCD Input |
|
| |
Common Serial (TTL) |
|
| |
RS232/RS485 |
|
| |
Communication Card |
|
| |
Motorized Pot |
|
| |
Pulse Input 1 |
|
| |
|
|
| |
Frequency Override Multiplying Input | Direct Access Number — | F661 | |
Program ⇒ Feedback Parameters ⇒ Override Control | Parameter Type — Selection List | ||
| Factory Default — Disabled |
|
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Changeable During Run — No
Selecting either of the input methods listed enables this feature. The selected input is used as a multiplier of the programmed Output Frequency.
If operating using the LED Keypad Option and Setting is selected, the value entered at F729 is used as the multiplier.
Settings:
Disabled
VI/II
RR
RX
RX2 (option)
Setting (LED Keypad Option Only)
162 | G7 ASD Operation Manual |