F210

F211

RR Speed Reference Setpoint #1 (%)

Program Frequency Setting Parameters Speed Reference Setpoints RR

This parameter is used to set the gain and bias of the RR input terminal when this terminal is used as the control input while operating in the Speed Control or the Torque Control mode.

Perform the following setup to allow the system to receive control input at the

RRterminal:

Program Fundamental Parameters Standard Mode Selection Command Mode Use Control Terminal Strip.

Program Fundamental Parameters Standard Mode Selection Frequency Mode #1 Use RR.

Provide a Run command (F or R).

Gain and Bias Settings

When operating in the Speed Control mode, the settings that determine the gain and bias of the RR terminal are:

RR Speed Reference Setpoint #1 (frequency) (F211),

the RR input signal level that represents RR Speed Reference Setpoint #1 (frequency): F210,

RR Speed Reference Setpoint #2 (frequency) (F213), and

the RR input signal level that represents RR Speed Reference Setpoint #2 (frequency): F212.

When operating in the Torque Control mode, the settings that determine the gain and bias of the RR terminal are:

Torque Reference Setpoint #1 (%) (F214),

the RR input signal level that represents the RR Torque Reference Setpoint #1 (%): F210,

Torque Reference Setpoint #2 (%) (F215), and

the RR input signal level that represents the RR Torque Reference Setpoint #2 (%): F212.

Direct Access Number — F210

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 100.0

Units — %

Frequency Settings

Torque Settings

Once set, as the RR input voltage changes, the output frequency or the output torque of the drive will vary in accordance with the above settings.

This parameter sets the RR input level that represents RR Speed Reference Setpoint #1 (torque or frequency). This value is entered as 0 – 100% of the 0 – 10 VDC RR input signal range.

The input signal may be trimmed using F472 (Bias) and F473 (Gain).

RR Speed Reference Setpoint #1 (frequency)

Direct Access Number — F211

Program Frequency Setting Parameters Speed Reference

Parameter Type — Numerical

Setpoints RR

Factory Default — 0.0

This parameter is used to set the gain and bias of the RR input terminal when

Changeable During Run — Yes

 

this terminal is used as the control input while operating in the Speed Control

Minimum — 0.0

mode.

Maximum — 100.0

 

See F210 for further information on this setting.

Units — Hz

This parameter sets the RR Speed Reference Setpoint #1 (frequency) and is

 

the frequency that is associated with the setting of F210.

 