Generac 13694330200 owner manual SIX-LEAD VAG, THREE-PHASE Stator, Field Wiring Requirements Table

Models: 13694330200

1 118
Download 118 pages 60.05 Kb
Page 11
Image 11

General Information

Figure 1.9 - Single-/Three-phase

Delta Stator Connection

E2

240V

240V

 

 

S6

I

 

 

 

 

SII

S3~

 

 

 

 

--240V ---- J

SIX-LEAD. 600 VAG, THREE-PHASE STATOR

This type of stator has three coils and six leads (Figure 1.10). Units may be assigned any of the following voltage codes:

"1.:' units are rated 346/600 VAG, three-phase, 60 Hertz.

"5" units are rated 277/480 VAG, three-phase, 50 Hertz.

Figure 1.10 - Six-lead Stator Connection

51

1 1

277V 50HZ 480V 50 HZ 346V60HZ 600V 60 HZ

!

S2

FIELD WIRING CONNECTIONS REQUIREMENTS

The table should be used as areference for: wire type, temperature rating, and size range of output wires to be connected to the circuit breakers. Wire sizes should be in accordance with table 310.16 of the National Electric Gode (NEG).

FIELD WIRING REQUIREMENTS TABLE

 

 

 

 

Circuit Breaker

 

 

Breaker Frame

Gircuit Breaker Range

Wire Type

Wire Temperature

Lug AWG Wire

Torque to Wire

(A)

Rating

Range / (Number of

 

 

 

 

 

 

 

 

Gonductors)

 

 

Series G- JG Frame

20 - 250

Cu

75c C

4-350 kemil (1)

180 in-Ib

Series G- LG Frame

160 - 600

Cu/AI

75C C

2-500 kemil (2)

3751n-lb

 

 

 

 

 

 

 

 

 

 

 

(#14-10) 35 In-Ib

 

15 - 100

Cu/AI

75c C

14-1/0 (1)

(#8) 40 In-Ib

 

(#6-4) 45 in-Ib

Series C- FFrame

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(#3-1/0) 50 in-Ib

 

60 - 200

CulAl

75c C

4-4/0 (1)

120 in-Ib

 

100 - 225

Cu/AI

75°C

6-300 kemll (1)

120 in-Ib

Series C- J Frame

250

Cu

75°C

4-350 kemll (1)

275

in-Ib

 

225

CulAl

75°C

3-350 kemll (1)

275

in-Ib

Series C- K Frame

300

CulAl

75DC

250-500 kemll (1)

375

In-Ib

 

350 - 400

Cu/AI

75D C

3/0-250 kemil (2)

2751n-lb

Series C- L Frame

450 - 500

Cu/AI

75°C

3/0-350 kemil (2)

275

in-Ib

600

Cu/AI

75°C

400-550 kemll (2)

275

in-Ib

 

Series C- M Frame

700 - 800

Cu/AI

WC

3/0-400 kemll (3)

3751n-lb

Series C- NFrame

900 - 1000

Cu/AI

75°C

4/0-500 kemll (4)

375 In-Ib

1200

Cu/AI

WC

500-750 kemil (3)

450 In-Ib

 

Series C- RFrame

1400 - 1600

Cu/AI

75°C

500-1000 kemil (4)

550

in-Ib

NOTE: All field installations must meet the National Electric Code for wire size and bending space requirements.