Generac 13694330200 owner manual Transfer Switch, Service Schedule, Retransfer and Shutdown

Models: 13694330200

1 118
Download 118 pages 60.05 Kb
Page 19
Image 19

 

 

Maintenance

~

Turn ON the utility power supply to the transfer switch, using

A The Maintenance Disconnect Switch and

 

the means provided (such as the utility power source main line

 

circuit breaker) .

.... the AUTO/OFF/MANUAL switches (if so

Let the generator run at no-load for a few minutes to stabilize

equipped) must be set properly, or the

 

internal temperatures.

generator will crank and start as soon as

Shut down the generator.

the UTILITY power to the transfer switch is

 

 

turned off. Refer to applicable control panel

OPERATING UNIT WITH AUTOMATIC

and transfer switch manuals for more infor-

mation.

TRANSFER SWITCH

A Do not proceed until certain that utility

If the generator has been installed along with an automatic transfer

.... source voltage is available to the transfer

switch, such as a GTS-type switch, the engine may be started and

switch and the transfer switch main contacts

stopped automatically or manually.

are set to UTILITY.

 

NOTE:

 

 

/r\ Do not attempt manual operation until all

Refer to the applicable manual for the transfer switch and to

illpower supplies to the transfer switch have

"Transfer Switch Start Signal Connections". In addition, please

been positively turned off, or extremely dan-

note the dangers under "Engine Start-up and Transfer."

gerous - possibly lethal - electrical shock

 

will result.

 

 

/i). Transfer switch enclosure doors should be ~kept closed and locked. Only authorized

personnel should be allowed access to the transfer switch Interior. Extremely high and dangerous voltages are present in the trans- fer switch.

In order to manually transfer load from the utility source to the generator, follow these directions:

Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit breaker).

Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.

Set the stationary emergency generator'smain line circuit breaker to its OFF (or OPEN) position.

Start the generator.

Let engine stabilize and warm up.

Check all applicable instrument and gauge readings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e, load circuits supplied by the generator.

Set the stationary emergency generator'smain line circuit breaker to its ON (or CLOSED) position.

Load circuits are now powered by the stationary emergency generator.

RETRANSFER AND SHUTDOWN

For additional information, refer to the applicable control panel manual for this unit, as well as any literature pertaining to the transfer switch.

To manually transfer the load back to the utility power source and shut down the generator, follow these directions:

Set the stationary emergency generator'smain line circuit breaker to its OFF (or OPEN) position.

Manually move the transfer switch handle to its UTILITY (NOR- MAL) position, i.e., load cirCUits connected to the utility.

SERVICE SCHEDULE

AUTHORIZED OPERATOR MAINTENANCE FUNCTIONS

Every Month or 100 Hours (whichever comes first)

Test stationary emergency generator system.

Inspect battery (batteries) and cables.

Check engine oil level.

Check gearbox oil level (if so equipped).

Check engine coolant level.

Check generator ground connections.

Test/inspect starting aids.

Every Three Months or Every 120 Hours (whichever comes first)

Inspect and test fuel system and connections.

Inspect exhaust system.

Inspect/test fuel supply system.

AUTHORIZED SERVICE TECHNICIAN MAINTENANCE FUNCTIONS

After First 30 Hours of Operation

Inspect Wiring.

Change engine crankcase oil and oil filter.

Inspect engine fan belts.

Inspect battery (batteries) and cables.

Every Six Months or Every 200 Hours (whichever comes first)

Lubricate engine controls.

Service engine air cleaner.

Service engine fuel filter.

Inspect AC generator.

Test engine safety controls.

Inspect fan belts.

Check engine coolant level.

Inspect engine cooling system hoses.

17

Page 19
Image 19
Generac 13694330200 owner manual Transfer Switch, Service Schedule, Retransfer and Shutdown